Carrier 58MSA Installation, Start-Up, And Operating Instructions Manual

4-way multipoise fixed-capacity condensing gas furnace sizes 040-120 series 150

Advertisement

Visit www.carrier.com
Installation, Start-Up, and Operating Instructions
A93040
NOTE: Read the entire instruction manual before starting the
installation.
This symbol → indicates a change since the last issue.
Index
DIMENSIONAL DRAWING........................................................3
SAFETY CONSIDERATIONS .....................................................2
Clearances to Combustibles......................................................4
CODES AND STANDARDS........................................................4
INTRODUCTION ..........................................................................5
APPLICATIONS............................................................................5
General ......................................................................................5
Upflow Applications.................................................................5
Downflow Applications ............................................................8
LOCATION..................................................................................13
General ....................................................................................13
Hazardous Locations...............................................................14
AIR FOR COMBUSTION AND VENTILATION ....................14
INSTALLATION .........................................................................17
Leveling Legs (If Desired) .....................................................17
Installation In Horizontal Applications ..................................19
Air Ducts.................................................................................20
General...............................................................................20
Ductwork Acoustical Treatment .......................................20
Supply Air Connections ....................................................20
Return Air Connections.....................................................20
Filter Arrangement..................................................................20
Bottom Closure Panel.............................................................21
Gas Piping...............................................................................21
Electrical Connections ............................................................22
115-v Wiring......................................................................22
24-v Wiring........................................................................24
Accessories ........................................................................24
Venting ....................................................................................24
Common Vent Systems................................................24
Combustion-Air and Vent Piping .....................................28
Vent Termination...............................................................35
Multiventing.......................................................................35
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
PC 101
Catalog No. 535-80138
Tab 6a 8a
For Sizes 040-120 Series 150
Page
Printed in U.S.A.
4-Way Multipoise Fixed-Capacity
Condensing Gas Furnace
As an ENERGY STAR®
Partner, Carrier Corpora-
tion has determined that
this product meets the EN-
ERGY STAR® guidelines
for energy efficiency.
HORIZONTAL
LEFT
AIRFLOW
Fig. 1-Multipoise Orientations
Condensate Drain....................................................................36
General...............................................................................36
Application.........................................................................36
Condensate Drain Protection.............................................36
General ....................................................................................37
Prime Condensate Trap With Water ......................................37
Purge Gas Lines......................................................................38
Sequence of Operation............................................................38
Heating Mode ....................................................................38
Cooling Mode ....................................................................39
Continuous Blower Mode .................................................39
Heat Pump Mode...............................................................39
Component Test.................................................................39
Adjustments.............................................................................40
Set Gas Input Rate ............................................................40
Set Temperature Rise ........................................................44
Blower Off Delay (Heat Mode)........................................45
Set Thermostat Heat Anticipator ......................................45
Form 58MSA-10SI
Pg 1
58MSA
ama
CERTIFIED
ISO 9001:2000
REGISTERED
AIRFLOW
UPFLOW
HORIZONTAL
RIGHT
DOWNFLOW
AIRFLOW
AIRFLOW
A93041
8-04
Replaces: 58MSA-9SI

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 58MSA

  • Page 1: Table Of Contents

    NOTE: Read the entire instruction manual before starting the REGISTERED installation. This symbol → indicates a change since the last issue. As an ENERGY STAR® Partner, Carrier Corpora- tion has determined that Index Page this product meets the EN- ERGY STAR® guidelines DIMENSIONAL DRAWING............3...
  • Page 2: Safety Considerations

    CHECKLIST................46 reliability, or operation. The 58MSA Multipoise Condensing Gas-Fired Furnaces are CSA SAFETY CONSIDERATIONS (formerly AGA and CGA) design-certified for natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages.
  • Page 4: Clearances To Combustibles

    INSTALLATION This forced air furnace is equipped for use with natural gas at altitudes 0 - 10,000 ft (0 - 3,050m), except 140 size furnaces are only approved for altitudes 0 - 7,000 ft. (0 - 2,135m). An accessory kit, supplied by the manufacturer, shall be used to convert to propane gas use or may be required for some natural gas applications. This furnace is for indoor installation in a building constructed on site.
  • Page 5: Electrostatic Discharge (Esd) Precautions

    7. An ESD service kit (available from commercial sources) may also be used to prevent ESD damage. INTRODUCTION The model 58MSA 4-way multipoise, Gas-Fired, Category IV, condensing furnaces are available in model sizes ranging in gas input rates of 40,000 to 120,000 Btuh.
  • Page 6 FURNACE BLOWER SHELF CONDENSATE DOOR TRAP FURNACE CONDENSATE DOOR FURNACE TRAP (INSIDE) FURNACE SIDE SIDE FIELD FIELD DRAIN DRAIN CONN CONN ALTERNATE DRAIN TUBE LOCATION SIDE VIEW FRONT VIEW END VIEW FRONT VIEW CONDENSATE TRAP DRAIN TUBE LOCATION HORIZONTAL DOWNFLOW AND ALTERNATE UPFLOW APPLICATIONS EXTERNAL UPFLOW APPLICATIONS APPLICATIONS...
  • Page 7 PLUG PLUG COLLECTOR BOX COLLECTOR BOX DRAIN TUBE (BLUE DRAIN TUBE (BLUE & WHITE STRIPED) & WHITE STRIPED) COLLECTOR BOX COLLECTOR BOX TUBE (PINK) TUBE (PINK) COLLECTOR BOX COLLECTOR BOX TUBE (GREEN) TUBE (GREEN) COLLECTOR BOX INDUCER HOUSING DRAIN TUBE (BLUE) (MOLDED) DRAIN TUBE (BEHIND COLLECTOR BOX...
  • Page 8: Downflow Applications

    Upper Inducer Housing Drain Connection Attached to the UPPER (unused) inducer housing drain connection FIRE, INJURY OR DEATH HAZARD is a cap and clamp. This cap is used to prevent condensate leakage Failure to follow this warning could result in electrical shock, in this application.
  • Page 9: Horizontal Left (Supply-Air Discharge) Applications

    (a.) Install drain tube coupling (factory-supplied in 2. Use smaller diameter tube (factory-supplied in loose parts loose parts bag) into collector box drain tube bag) to extend collector box pressure tube (green label) which (blue and white striped label) which was previ- was previously connected to condensate trap relief port ously plugged.
  • Page 10 PLUG COLLECTOR BOX AUXILIARY "J" BOX DRAIN TUBE (BLUE AND WHITE STRIPED) CONDENSATE COLLECTOR BOX TRAP TUBE (GREEN) INDUCER HOUSING COLLECTOR DRAIN TUBE (VIOLET) BOX EXTENSION COLLECTOR BOX DRAIN TUBE DRAIN TUBE (BLUE) COLLECTOR BOX EXTENSION TUBE DRAIN TUBE COUPLING COLLECTOR BOX TUBE (PINK) RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR 040, 060, AND 080 HEATING INPUT FURNACES...
  • Page 11: Horizontal Right (Supply-Air Discharge) Applications

    A 3-IN. MINIMUM CLEARANCE VENT TO COMBUSTION-AIR INTAKE IS REQUIRED. COMBUSTION–AIR INTAKE A 12-IN. MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE. 30-IN. MIN WORK AREA ″...
  • Page 12 COLLECTOR BOX DRAIN TUBE (BLUE) COLLECTOR BOX TUBE (GREEN) COLLECTOR BOX EXTENSION TUBE PLUG COLLECTOR BOX TUBE (PINK) AUXILARY “J” BOX RELOCATED HERE CONDENSATE TRAP COLLECTOR BOX DRAIN TUBE (BLUE AND WHITE STRIPED) INDUCER HOUSING DRAIN TUBE (VIOLET) COLLECTOR BOX EXTENSION TUBE A00214 Fig.
  • Page 13: Location

    FRONT LEVEL (0″) FRONT FRONT ⁄ ″ ⁄ ″ MAX ⁄ ″ MAX UPFLOW OR DOWNFLOW HORIZONTAL BACK A02146 Fig. 13—Furnace Location for Proper Condensate Drainage FRONT A93043 NOTE: A 12-in. minimum horizontal pipe section is recom- mended with short (5 to 8 ft) vent systems. This recommendation Fig.
  • Page 14: Hazardous Locations

    32°F MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED 18-IN. MINIMUM TO BURNERS A93044 Fig. 16—Installation in a Garage A93058 Fig. 15—Freeze Protection FURNACE CORROSION HAZARD Air for combustion must not be contaminated by halogen compounds, which include fluoride, chloride, bromide, and FIRE, INJURY OR DEATH HAZARD iodide.
  • Page 15 → Table 1—Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors TWO HORIZONTAL DUCTS SINGLE DUCT OR OPENING TWO OPENINGS OR VERTICAL DUCTS (1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW) (1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW) (1 SQ.
  • Page 16 Indoor Combustion Air© NFPA & AGA of the total input rating of all gas appliances in the space, but not less than 100 in. (0.06 m ). One opening shall Standard and Known-Air-Infiltration Rate Methods commence within 12″ (300 mm) of the ceiling and the Indoor air is permitted for combustion, ventilation, and dilution, second opening shall commence within 12″...
  • Page 17: Installation

    1 SQ IN. PER 4000 DUCTS BTUH* OUTDOORS CIRULATING AIR VENT THROUGH ROOF DUCTS 12″ MAX 12″ 1 SQ IN. VENT PER 2000 THROUGH 12″ MAX BTUH* ROOF 1 SQ IN. 1 SQ IN. 4000 PER 1000 BTUH* BTUH * IN DOOR OR WALL DUCTS UNCONFINED...
  • Page 18 PLENUM OPENING FLOOR OPENING A96283 Fig. 20—Floor and Plenum Opening Dimensions FURNACE FURNACE (OR COIL CASING WHEN USED) CD5 OR CK5 COIL ASSEMBLY OR KCAKC COIL BOX COMBUSTIBLE COMBUSTIBLE FLOORING FLOORING DOWNFLOW SUBBASE SHEET METAL PLENUM SHEET METAL PLENUM FLOOR FLOOR OPENING OPENING...
  • Page 19: Installation In Horizontal Applications

    PERFORATED → DISCHARGE DUCT UNIT MAY NOT OPERATE FLANGE Failure to follow this caution could result in intermittent unit operation. Do not bend duct flanges inward as shown in Fig. 23. This will affect airflow across heat exchangers and may cause limit cycling or premature heat exchanger failure.
  • Page 20: Air Ducts

    3/8-in. lockwashers, and 3/8-in. nuts on hanger rods as shown in Horizontal Furnaces Fig. 24. Dimples are provided for hole locations. (See Fig. 2.) Connect supply-air duct to supply air opening on furnace. The supply-air duct attachment must ONLY be connected to furnace Step 4—Air Ducts supply/outlet or air conditioning coil casing (when used).
  • Page 21: Bottom Closure Panel

    Table 4—Filter Information 21-IN. WIDE ⁄ -IN. WIDE CASINGS ONLY: CASINGS ONLY: SUPPORT RODS (3) FURNACE FILTER SIZE (IN.)* FILTER TYPE INSTALL FIELD-SUPPLIED EXTEND 1/4" ON EACH CASING FRAMED FILTER FILLER STRIP Side Return Bottom Return SIDE OF FILTER AND WIDTH (IN.) UNDER FILTER.
  • Page 22: Electrical Connections

    be a separate line running directly from meter to furnace, if possible. Refer to Table 5 for recommended gas pipe sizing. Risers SUPPLY must be used to connect to furnace and to meter. Support all gas MANUAL piping with appropriate straps, hangers, etc. Use a minimum of 1 SHUTOFF hanger every 6 ft.
  • Page 23 Table 6—Electrical Data OPERATING VOLTS— UNIT UNIT MAX WIRE MAX FUSE OR VOLTAGE RANGE HERTZ— UNIT WIRE SIZE AMPACITY† LENGTH (FT)‡ CKT BKR AMPS** PHASE AMPS SIZE Max* Min* 040-08 115—60—1 040-12 115—60—1 10.0 060-08 115—60—1 060-12 115—60—1 060-16 115—60—1 12.8 080-12 115—60—1...
  • Page 24: 24-V Wiring

    Make field 24-v thermostat connections at 24-v terminal block on furnace control. For proper cooling operation, Y wire from The 58MSA Furnaces require a dedicated, (one 58MSA furnace thermostat MUST be connected to Y terminal on furnace control, only) sealed vent system. All air for combustion is taken from the as shown in Fig.
  • Page 25 Table 8—Maximum Allowable Pipe Length (ft) NUMBER OF 90° ELBOWS TERMINATION PIPE DIA ALTITUDE (FT) UNIT SIZE TYPE (IN.)* 040-08 2 Pipe or 2-in 1-1/2 040-12 Concentric 060-08 1-1/2 2 Pipe or 2-in 060-12 Concentric 060-16 1-1/2 080-12 2 Pipe or 2-in 080-16 0 to 2000 Concentric...
  • Page 26 Table 8—Maximum Allowable Pipe Length (ft) (Continued) NUMBER OF 90° ELBOWS TERMINATION PIPE DIA ALTITUDE (FT) UNIT SIZE TYPE (IN.)* 1-1/2 040-08 2 Pipe or 2-in 040-12 Concentric 060-08 1-1/2 2 Pipe or 2-in 060-12 Concentric 060-16 080-12 2 Pipe or 2-in 4001 to 5000‡...
  • Page 27 Table 8—Maximum Allowable Pipe Length (ft) (Continued) NUMBER OF 90° ELBOWS TERMINATION PIPE DIA ALTITUDE (FT) UNIT SIZE TYPE (IN.)* 1-1/2 040-08 2 Pipe or 2-in 040-12 Concentric 060-08 1-1/2 2 Pipe or 2-in 060-12 Concentric 060-16 080-12 2 Pipe or 2-in 8001 to 9000‡...
  • Page 28: Combustion-Air And Vent Piping

    FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-V WIRING NOTE 2 THERMOSTAT FIVE WIRE FIELD-SUPPLIED TERMINALS DISCONNECT THREE-WIRE HEATING-ONLY 208/230- OR BLOWER DOOR SWITCH 460-V THREE PHASE 208/230-V SINGLE PHASE AUXILIARY 115-V FIELD- J-BOX SUPPLIED NOTE 1 DISCONNECT CONDENSING...
  • Page 29 Table 9—Maximum Allowable Exposed Vent Pipe Length (ft) With and Without Insulation in Winter Design Temperature Ambient* WINTER DESIGN MAX PIPE FURNACE WITHOUT WITH 3/8–IN. OR TEMPERATURE DIAMETER SIZE INSULATION THICKER INSULATION† (°F) (IN.) * Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length as specified in Table 9.
  • Page 30 25--24--65--2 AIR SUPPL Y INLET VENT TERMINAL AREA WHERE TERMINAL IS NOT PERMITED Item Clearance Descriptions Canadian Installation (1) U.S. Installation (2) Clearance above grade, veranda, porch, deck, balcony, or 12˝ (30cm) # 12˝ (30 cm) anticipated snow level 6˝ (15 cm) for appliances ≤ 10,000 BTUH (3kW), 12˝ (30 Clearance to a window or door that may be opened 4´...
  • Page 31 PRINTED CIRCIUT BOARD PRINTED CIRCIUT BOARD...
  • Page 32 TWINNING AND/OR COMPONENT TEST BLOWER OFF-DELAY TERMINAL J2 JUMPER BLOWER OFF-DELAY HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX.) 24-V THERMOSTAT TERMINALS TRANSFORMER 24-VAC CONNECTIONS TEST/TWIN 0.5 AMP@24VAC 3-AMP FUSE FUSE 3-AMP SEC-2 SEC-1 LED OPERATION & EAC-2 DIAGNOSTIC LIGHT PL1-LOW VOLTAGE MAIN HARNESS CONNECTOR 115-VAC(L2)NEUTRAL CONNECTIONS...
  • Page 33 NOTE: Select 1 vent pipe connection and NOTE: Select 1 vent pipe connection and FIELD-SUPPLIED 1 combustion-air pipe connection. 1 combustion-air pipe connection. 2-IN. DIAMETER FIELD-SUPPLIED PVC 90° ELBOW 2-IN. DIAMETER FLOW PVC PIPE COMBUSTION- COMBUSTION- VENT VENT VENT VENT COMBUSTION- COMBUSTION- FLOW...
  • Page 34 UNIT MAY NOT OPERATE CARBON MONOXIDE AND PROPERTY DAMAGE Failure to follow this caution may result in intermittent unit HAZARD operation. Failure to follow this warning could result in property When vent pipe is exposed to temperatures below freezing, damage, personal injury, or death. such as when it passes through an unheated space or when a Vent pipes must be airtight and watertight.
  • Page 35: Vent Termination

    MULTIVENTING NOTE: See label on vent extension pipe for proper installation. When 2 or more 58MSA Furnaces are vented near each other, each This pipe may be shortened if an elbow is used to connect vent furnace must be individually vented. NEVER common vent or extension tube to field-installed vent pipe.
  • Page 36: Condensate Drain

    Step 10—Condensate Drain GENERAL Condensate trap is shipped installed in the blower shelf and factory connected for UPFLOW applications. Condensate trap must be RELOCATED for use in DOWNFLOW and HORIZONTAL applications. ROOF Condensate trap MUST be used for all applications. An external trap is not required when connecting the field drain to this condensate trap.
  • Page 37: Start-Up, Adjustments And Safety Check

    NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, furnace control fault indicator light will flash rapidly and furnace will not operate. 2. Thermostat wire connections at terminals R, W, G, and Y must be made at 24-v terminal block on furnace control center. 3.
  • Page 38: Purge Gas Lines

    Step 4—Sequence of Operation 2. Connect field-supplied 1/2-in. ID tube to upper inducer housing drain connection. 3. Insert field-supplied funnel into tube. → FURNACE MAY NOT OPERATE 4. Pour 1 quart of water into funnel/tube. Water should run Failure to follow this caution may result in furnace operation through inducer housing, overfill condensate trap, and flow stopping and water pipes freezing during cold weather.
  • Page 39: Heating Mode

    If flame is proved when flame should not be present, the 4. Heat Pump Mode furnace control CPU will lock out of Gas-Heating mode When installed with a heat pump, the furnace control auto- and operate the inducer motor IDM until flame is no longer matically changes the timing sequence to avoid long blower proved.
  • Page 40: Adjustments

    NOTE: This furnace has been approved for a manifold pressure c. Verify furnace model. Table 11 can only be used for model 58MSA furnaces. of 3.2 in. wc to 3.8 in. wc when installed at altitudes up to 2000 ft.
  • Page 41 Table 11—Model 58MSA Orifice Size and Manifold Pressure for Correct Input (Tabulated Data Based on 20,000 Btuh per Burner, Derated 2% for Each 1000 Ft Above Sea Level)* SPECIFIC GRAVITY OF NATURAL GAS AVG GAS ALTITUDE HEAT VALUE 0.58 0.60 0.62...
  • Page 42 Table 11—Model 58MSA Orifice Size and Manifold Pressure for Correct Input Continued (Tabulated Data Based on 20,000 Btuh per Burner, Derated 2% for Each 1000 Ft Above Sea Level)* SPECIFIC GRAVITY OF NATURAL GAS AVG GAS ALTITUDE HEAT VALUE 0.58 0.60...
  • Page 43 Table 11—Model 58MSA Orifice Size and Manifold Pressure for Correct Input Continued (Tabulated Data Based on 20,000 Btuh per Burner, Derated 2% for Each 1000 Ft Above Sea Level)* SPECIFIC GRAVITY OF NATURAL GAS AVG GAS ALTITUDE HEAT VALUE 0.58 0.60...
  • Page 44: Set Temperature Rise

    Table 13—Gas Rate (Cu Ft/Hr) SIZE OF TEST DIAL SIZE OF TEST DIAL SECONDS SECONDS FOR 1 FOR 1 REVOLUTION REVOLUTION cu ft cu ft cu ft cu ft cu ft cu ft 1800 1636 1500 1385 1286 1200 1125 1059 1000 BURNER...
  • Page 45: Blower Off Delay (Heat Mode)

    2. When thermometer readings stabilize, subtract return-air tem- Table 15—Blower Off Delay Setup Position perature from supply-air temperature to determine air tem- PINS 1 AND 2 2 AND 3 3 AND 4 4 AND 5 perature rise. Time (in sec) 3.
  • Page 46 CHECKLIST 1. Put away tools and instruments. Clean up debris. 2. Verify flame rollout manual reset switch has continuity. 3. Verify that blower and main access doors are properly installed. 4. Cycle test furnace with room thermostat. 5. Check operation of accessories per manufacturer’s instruc- tions.
  • Page 47 CHECKLIST—INSTALLATION LOAD CALCULATION Condensate Drain ____________ Heating Load (Btuh) ________ Unit Level or Pitched Forward ____________ Cooling Load (Btuh) Internal Tubing Connections Free of Kinks ________ and Traps ____________ Furnace Model Selection External Drain Connection Leak Tight and ________ Sloped VENT PIPING ________ Condensate Trap Primed before Start-Up...
  • Page 48 Copyright 2004 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 58msa10si Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book 1 4 PC 101 Catalog No. 535-80138 Printed in U.S.A.

Table of Contents