Burner installation

Separate burner documenta-
tion.
Boiler size
Minimum
mm
flame tube
length
7
Max. flame
tube diameter,
mm
dimension e
3. Trim thermal insulation D in
accordance with the actual flame
tube diameter.
4. Seal the annular gap between the
flame tube and the thermal insula-
tion block with heat-resistant insu-
lation material E (supplied in the
combustion chamber pack).
1. Secure burner plate A for the
burner installation together with
seal ring C to boiler flange B.
Note
If the burner plate was not pre-
drilled at the factory, drill the burner
fixing holes into the burner plate
and cut out the flame tube hole.
For the max. flame tube diameter,
see the table.
2. Secure the burner to the burner
plate.
1
2
3
Burner connection dimensions
515
595
715
715
5. Run the cable/leads and the fuel oil
line etc. in a loop. This enables the
cleaning door to be opened without
lines/cables/leads having to be
removed.
4
5
6
360
765
765
910
7
8
1015
13