Boiler Location And Clearances; Installation; Installation And Servicing Clearances; Compartments - Worcester 27Ri Compact Installation, Commissioning And Servicing Instructions

Wall hung rsf gas fired condensing regular boiler greenstar ri compact series
Hide thumbs Also See for 27Ri Compact:
Table of Contents

Advertisement

Minimum hole size for the condensate soak away must be
400mm deep by 300mmØ .
In situations where there are likely to be extremes of temperature or
exposure, the use of a proprietary trace-heating system for external pipe
work, incorporating an external frost thermostat, should be considered.
If such a system is used, the requirement to use 32mm pipe does not
apply. However, all other guidance above and the instructions for the
trace heating system, should be closely followed.
NOTICE: Unheated internal areas.
▶ Internal pipe runs in unheated areas such as lofts,
basements and garages should be treated as external
runs and consideration should be given to using a
CondenseSure siphon.
14
*
1
7
Fig. 9 Condensate pump to external disposal
*
1
500mm min.
13
14
9
11
12
Fig. 10 Soak away
3.5

BOILER LOCATION AND CLEARANCES

3.5.1 INSTALLATION

This boiler is only suitable for installing internally within a property at a
suitable location onto a fixed, rigid surface at least the same size as the
boiler and capable of supporting the boiler weight.
NOTICE:
No surface protection is required against heat transfer
from the boiler
Greenstar Ri Compact 6 720 646 610 (2013/12)

3.5.2 INSTALLATION AND SERVICING CLEARANCES

Figure 11 shows the minimum space required to install and service the
boiler in a compartment.
13
Fig. 11 Unventilated compartment
25mm min.
[*]
[**]
[***] Height for either 60/100 flue or 80/125 flue
6720644744-12.2Wo

3.5.3 COMPARTMENTS:

Follow the requirements of BS6798 and BS5440 Part 2 and note:
• Minimum clearances must be maintained.
9
• An access door is required to install, service and maintain the boiler
and any ancillary equipment.
10
• If fitting the boiler into an airing cupboard use a non-combustible
material to separate the boiler from the airing space.
The material can be perforated up to a maximum hole size of 13mm.

3.5.4 BATHROOMS

The appliance may be installed outside the shaded area, and in zone 2.
Additional RCD (Residual Current Device) protection may be required.
Refer to the latest IEE wiring regulations.
25mm min.
400mm
min.
10
Fig. 12 Bathroom installations
870mm
20mm*
600mm**
5mm
400mm
Minimum clearance to removable door
Minimum clearance required for servicing
Radius 600mm
PRE-INSTALLATION
170/210mm***
5mm
200mm
290mm
6720646608-124.3Wo
13