Spigot & Spigot Extension; Pre-Cast Flue; Installation; Unpack The Fire - Potterton Hallmark Installation & Service Instructions Manual

Radiant convector gas fire
Table of Contents

Advertisement

3. Installation Requirements - Page 6

4. Installation

6 Installation Requirements/Installation
Supplied By www.heating spares.co Tel. 0161 620 6677
3.6. Spigot & Spigot Extension
The flue spigot or spigot extension MUST pass through the
closure plate by at least 25mm and have a minimum
clearance of 50mm between its opening & the nearest
obstruction.

3.7. Pre-Cast Flue

The fire is suitable for fitting into a properly constructed non
impeded pre-cast flues at least 3m high.

4.1. Unpack The Fire

The pack contains:
1
Fire Assembly (with radiants)
2
Flue Spigot
3
Spigot Restrictor
4
Closure plate
5
Cooler Plate
6
Poly Bag Assembly
7
Reply Card
If any parts are damaged or missing please contact the
phone number shown on the check lists supplied with the
packs.
Do Not discard the packaging until all items are
accounted for or the fire is installed.
4.2. Pre-Cast Flue
Note: It must be emphasised that no mortar fangs between
the blocks should be extruded into the flue way. If raking
blocks are used they must be fitted according to the
manufacturers instructions. Mortar MUST NOT be allowed
to drop down and accumulate in the raked positions.
The spigot restrictor should NOT be fitted.
The cooler plate supplied must be formed at the markings
on the plate shown in Fig. 7.
Then fix to the rear face of the closure plate using the
screws provided. See Fig. 7.
Part No. 900/9350/1