Setting an indoor unit installation option (suitable for the condition of each installation location)
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional
power supply in the indoor unit.
2. Set the installation option according to the installation condition of an
air conditioner.
- The default setting of an indoor unit installation option is "020010-101000-
220010-300000".
3. Set the indoor unit option by wireless remote controller.
02 series installation option
SEG1
SEG2
0
SEG7
SEG8
1
SEG13
SEG14
2
External control
SEG19
SEG20
3
• Number of hours using filter( SEG18) will be set to '1000hour' if SEG18 is set to any value other than 2 or 6.
• When setting the option other than above SEG values, the option will be set as "0".
• SEG5 central control option is set as 1 (Use) by default, so you don't need to set the central control option additionally.
However, if the central control is not connected but it doesn't indicate an error message, you need to set the central
control option as 0 (Disuse) to exclude the indoor unit from the central control.
• The heater output in SEG9 is generated from the hot coil part of the terminal board and is connected to the aux. heat
output harness for Samsung, internal electric heat options.
AM0**JNZDCH/AA IM ENG_V1.5_07082015
SEG3
External room temperature sensor
2
-
SEG9
Heater output
-
SEG15
-
SEG21
Heating setting
-
compensation
SEG4
/ Minimizing fan operation when
thermostat is off
SEG10
-
SEG16
-
SEG22
EEV Step of stopped unit during
oil return/defrost mode
37
SEG5
SEG6
Central control
-
SEG11
SEG12
EEV Step when
-
heating stops
SEG17
SEG18
-
-
SEG23
SEG24
-
-