Setting an indoor unit address and installation option
Setting an indoor unit address (MAIN/RMC)
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional
power supply in the indoor unit.
2. Before installing the indoor unit, assign an address to the indoor unit
according to the air conditioning system plan.
3. Assign an indoor unit address by wireless remote controller.
- The initial setting status of indoor unit ADDRESS(MAIN/RMC) is
"0A0000-100000-200000-300000" (address: 00, RMC1: 0, RMC2: 0).
Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
Explanation
PAGE
Remote
Controller
Display
Indication
Indication and
Details
0
Option
SEG7
Explanation
PAGE
Remote
Controller
Display
Indication
Indication and
Details
1
• When "A"~"F" is entered to SEG5~6, the indoor unit MAIN ADDRESS is not changed.
• If you set the SEG 3 as 0, the indoor unit will maintain the previous MAIN ADDRESS even if you input the
CAUTION
option value of SEG5~6.
• If you set the SEG 9 as 0, the indoor unit will maintain previous RMC ADDRESS even if you input the
option value of SEG11~12.
• You cannot set SEG11 and SEG12 as F value at the same time.
AM0**JNZDCH/AA IM ENG_V1.5_07082015
SEG2
MODE
Setting Main address
Details
Indication
Details
Indication
0
A
1
SEG8
Setting RMC address
Details
Indication
-
0
1
SEG3
SEG4
100-digit of indoor
10-digit of indoor unit
unit address
Details
Indication
Details
Indication
No Main
address
Main
0~9
100 -digit
address
setting
mode
SEG9
SEG10
Details
Indication
-
No RMC
address
RMC
address
setting
mode
36
SEG5
SEG6
The unit digit of an
indoor unit
Details
Indication
Details
0~9
10 -digit
0~9
A unit digit
SEG11
SEG12
Group channel(*16)
Group address
Details
Indication
Details
RMC1
0~F
RMC2
0~F