EXTERNAL OUTPUT
z
Compressor status output
•
Compressor operation status signal can be output by means of the following on-site work.
Circuit diagram example
Outdoor
control PC board
Connector
+
Red
1
White
2
Black
3
*10 m
Surely insulate with
insulation tape etc. since
this wire is not used.
* Make the distance from the PC board to the connected unit within 10 m.
Compressor status
Output Signal
Parts (Optional)
Parts name
External connect kit
Wire (External output) : Red / White / Black
Connected unit
Vcc
Vcc
Power
supply
+
Load
-
Signal
Field supply
Operation
Stop
ON
OFF
Model name
UTY-XWZXZ2
- (OU01 - 17) -
1) Power supply
●Voltage (Chart sign=Vcc) : DC 24V or less
2) Load
● Load : DC 20mA or less
Outdoor unit / Single phase