Registering the System
Before selecting Submit in Step 4 of the online registration
process, the following steps must be completed.
To register or re-register the Ethernet Interface
module:
1.
Open the panel cover.
2.
Enter Utility Access Code 1 (Dealer Code) if you are not
already in program mode.
3.
Press Option #.
4.
Press Test. The system will begin listing the remote
options and their values.
5.
Listen until you hear the phrase "Remote Option 1 is off."
Important: Remote Option 1 must be off in order for the
module to register successfully.
6.
Press Cancel to stop the panel from announcing option
values.
7.
Press Add.
8.
Press Option #.
9.
Press Test.
10. Press Option # repeatedly until you will hear the panel
announce "Remote Option 2".

Programming Options Reference

The following options are used to customize the Ethernet Interface module and are programmed at the panel
Table 1: Programming options
Option No.
Option
Simon Option 89
Serial Port Protocol
Simon Option 90
Comm Channel 1 Reports
Simon Option 91
Comm Channel 2 Reports
Simon Option 92
Comm Channel 3 Reports
Remote Option 1
Module Registration Status
Remote Option 2
Register Module Command
Remote Option 3
Dealer ID
Remote Option 4
Line Number
Remote Option 5
DHCP On/Off
Remote Option 6
Reset Module Command
Remote Option 7
Static Module IP Address
Remote Option 8
Static Router IP Address
Remote Option 9
Static Subnet Mask
Remote Option 10
Current Module IP Address
Ethernet Interface Installation Instructions
11. Press Done. The panel announces "Remote Option 2 OK."
Wait 30 seconds before proceeding to Verify Registration.
Verify Registration
To verify the system was registered properly at the
panel:
1.
Press Option #.
2.
Press Test. The system will begin listing the remote
options and their values.
3.
Listen until you hear the phrase "Remote Option 1 is on."
4.
Press Cancel so stop the panel from announcing option
values.
If the panel says "Remote Option 1 is off", the system was not
registered properly. Verify all connections are correct, Simon
Option 89 is On, the LED's on the module and Ethernet
connector are flashing (must open panel cover to verify), and
the Account Number is not already in use; then try to register
the system again. See the Troubleshooting section for more
information.
To verify the system was registered properly:
Follow the procedures on the premisesconnect.com website.
Default
Range
Off
On/Off
Off
0, 1, Off
Off
0, 1, Off
Off
0, Off
Off
On/Off
N/A
N/A
000
1-10-digit numeric
0001
1-10 digit numeric
On
On/Off
N/A
N/A
192.168.000.049
12-digit, 4 octet
192.168.000.001
12-digit, 4 octet
255.255.255.000
12-digit, 4 octet
Dynamic
12-digit numeric
Desired Setting
5