Table 12—Orifice Size* and Manifold Pressure For Gas Input Rate
(Tabulated Data Based On 21,000 Btuh Per Burner, Derated 4 Percent For Each 1000 Ft Above Sea Level)
ALTITUDE
RANGE
(FT)
0
to
2000
ALTITUDE
RANGE
(FT)
U.S.A.
Altitudes
2001
to
3000
or
Canada
Altitudes
2000
to
4500
ALTITUDE
RANGE
(FT)
3001
U.S.A. Only
to
4000
ALTITUDE
RANGE
(FT)
4001
to
5000
* Orifice numbers 43 are factory installed
d. BRIEFLY remove insulated terminal wire from the draft
safeguard (DSS) switch until LED goes out, then reconnect
it.
NOTE: If wire to LS or DSS is disconnected longer than 4 sec,
main blower starts, and retrieval request is ignored.
AVG GAS
0.58
HEAT VALUE
Orifice
Manifold
(BTU/CU FT)
No.
Pressure
900
42
925
43
950
43
975
43
1000
44
1025
44
1050
44
1075
45
1100
46
AVG GAS
0.58
HEAT VALUE
Orifice
Manifold
(BTU/CU FT)
No.
Pressure
800
43
825
43
850
43
875
43
900
43
925
43
950
43
975
43
1000
43
AVG GAS
0.58
HEAT VALUE
Orifice
Manifold
(BTU/CU FT)
No.
Pressure
775
43
800
43
825
43
850
43
875
43
900
43
925
43
950
43
AVG GAS
0.58
HEAT VALUE
Orifice
Manifold
(BTU/CU FT)
No.
Pressure
750
43
775
43
800
43
825
43
850
43
875
43
900
43
925
43
SPECIFIC GRAVITY OF NATURAL GAS
0.60
Orifice
Manifold
No.
Pressure
3.2
42
3.3
3.7
43
3.8
3.5
43
3.6
3.3
43
3.4
3.6
43
3.3
3.4
44
3.6
3.3
44
3.4
3.8
44
3.2
3.8
45
3.7
SPECIFIC GRAVITY OF NATURAL GAS
0.60
Orifice
Manifold
No.
Pressure
3.8
42
3.2
3.5
43
3.7
3.3
43
3.5
3.2
43
3.3
3.0
43
3.1
2.8
43
2.9
2.7
43
2.8
2.5
43
2.6
2.4
43
2.5
SPECIFIC GRAVITY OF NATURAL GAS
0.60
Orifice
Manifold
No.
Pressure
3.5
43
3.7
3.3
43
3.4
3.1
43
3.2
2.9
43
3.0
2.8
43
2.9
2.6
43
2.7
2.5
43
2.6
2.4
43
2.4
SPECIFIC GRAVITY OF NATURAL GAS
0.60
Orifice
Manifold
No.
Pressure
3.3
43
3.4
3.1
43
3.2
2.9
43
3.0
2.7
43
2.8
2.6
43
2.7
2.4
43
2.5
2.3
43
2.4
2.2
43
2.2
2. When above items have been completed, the LED flashes
status code 4 times. Record this status code for further
troubleshooting.
3. Check LED status. If no previous faults in history, control will
flash status code 11.
41
0.62
Orifice
Manifold
Orifice
No.
Pressure
No.
42
3.4
42
42
3.2
42
43
3.7
43
43
3.5
43
43
3.4
43
43
3.2
43
44
3.5
43
44
3.3
44
44
3.2
44
0.62
Orifice
Manifold
Orifice
No.
Pressure
No.
42
3.3
42
43
3.8
42
43
3.6
43
43
3.4
43
43
3.2
43
43
3.0
43
43
2.9
43
43
2.7
43
43
2.6
43
0.62
Orifice
Manifold
Orifice
No.
Pressure
No.
43
3.8
42
43
3.5
43
43
3.3
43
43
3.1
43
43
3.0
43
43
2.8
43
43
2.7
43
43
2.5
43
0.62
Orifice
Manifold
Orifice
No.
Pressure
No.
43
3.5
43
43
3.3
43
43
3.1
43
43
2.9
43
43
2.8
43
43
2.6
43
43
2.5
43
43
2.3
43
0.64
Manifold
Pressure
3.5
3.3
3.8
3.7
3.5
3.3
3.2
3.4
3.3
0.64
Manifold
Pressure
3.4
3.2
3.7
3.5
3.3
3.1
2.9
2.8
2.7
0.64
Manifold
Pressure
3.2
3.7
3.4
3.2
3.1
2.9
2.7
2.6
0.64
Manifold
Pressure
3.6
3.4
3.2
3.0
2.8
2.7
2.5
2.4