Bradford White Brute BNTH Installation And Operation Instructions Manual page 68

Hide thumbs Also See for Brute BNTH:
Table of Contents

Advertisement

Page 64
27
Internal fault:
Flame rod
shorted to
ground detected
28
Internal fault:
A/D linearity
test fails
29
Internal fault:
Flame bias
cannot be set in
range
30
Internal fault:
Flame bias
shorted to
adjacent pin
31
Internal fault:
SLO electronics
unknown error
32-46 Internal fault:
Safety Key 0
through 14
47
Flame Rod to
ground leakage
48
Static fl ame (not
fl ickering)
49
24 VAC voltage
low/high
50
Modulation fault
51
Pump fault
52
Motor
tachometer fault
53
AC input phases
reversed
59
Internal Fault:
Mux pin shorted
61
Anti short cycle
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
H
1. Check the module and display connections.
2. Check the module power supply and make sure that frequency, voltage
and VA meet the specifi cations.
H
Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.
H
Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.
H
Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.
L
1. Check the module and display connections.
2. Check the module power supply and make sure that both frequency
and voltage meet the specifi cations.
3. On 24 VAC applications, assure that J4 terminal 10 and J8 terminal 2
are connected together.
L
Internal Fault.
1. Reset module.
2. If fault repeats, replace module.
H
Will not be a lockout fault. Hold Only.
B
W
RADFORD
HITE

Advertisement

Table of Contents
loading

This manual is also suitable for:

Brute bntv

Table of Contents