Safety Rules; Transport / Storage; Fcc Compliance Statement - GE VH UL series User Manual

On-line
Table of Contents

Advertisement

1.3

SAFETY RULES

CAUTION! RISK OF ELECTRIC SHOCK
The UPS has an internal battery supply with a nominal voltage of 36/72Vdc (see chapter 8). The
appliance outlets may be electrically live, even when the UPS is disconnected from the mains.
The UPS contains potentially hazardous voltages. Do not open the unit, there are no user serviceable
parts inside.
CAUTION
There may be damage to the equipment if procedures and practices are not strictly observed and
followed.
NOTE
Do not attempt to service the UPS unless you have had proper training. Refer all maintenance and
servicing to properly qualified, skilled and competent service personnel.
Qualified, skilled personnel are persons who (because of their training, experience, and position as well as their
knowledge of appropriate standards, regulations, health and safety requirements and working conditions) are authorised
to be responsible for the safety of the equipment, at all times whilst carrying out their normal duties and are therefore
aware of, and can report, possible hazards (observe IEC 60364 and national wiring regulations and accident prevention
rules).
1.4

TRANSPORT / STORAGE

WARNING!
Please consider the weight of the UPS. Lift the box with the help of a second person; never try to lift it
by yourself!
 No liability can be accepted for any transport damage when the equipment is shipped in non-original packaging.
 Store the UPS in a dry location with the batteries in a fully charged state. Storage temperature must be within
-4 and 122F (-20 and +50 C). If the unit is stored for a period exceeding 3 months, optimal battery lifetime is
obtained if the storage temperature does not exceed 86F (30C).
 If the unit is stored for an extended period of time, the batteries must be recharged periodically. Connect the unit to a
wall outlet and recharge the batteries for 24 hours:
-
if the storage temperature is within -4 and 86F (-20 and +30°C): every 12 months,
-
if the storage temperature is within -4 and 122F (-20 and +50°C): every 3 months.
CAUTION
In case of storage, pay attention to:
1.5

FCC COMPLIANCE STATEMENT

Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of
the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment
is operated in a residential environment. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
Modifications not expressly approved by the manufacturer could void the user's authority to operate the equipment under
FCC rules.
Modifications reserved
GE_UPS_OPM_VHU_0K7_3K0_XUS_V011.docx
Critical Power
Operating Manual VH700 UL, VH1000 UL, VH1500 UL, VH2000 UL & VH3000 UL
Page 5/25