Troubleshooting - Monessen Hearth SDV500 Installation And Operating Instructions Manual

Table of Contents

Advertisement

TROUBLESHOOTING

STANDING PILOT IGNITION
SYMPTOM
POSSIBLE CAUSE
1. Spark ignitor
A. Wire disconnected.
will not light
pilot after
B. Defective ignitor.
repeated trig-
gering of
C. No gas or low gas pressure.
piezo.
D. No Propane/LPG in tank
2. Pilot will not
A. Defective thermocouple
stay lit after
carefully fol-
lowing light-
ing instruc-
tions.
B. Defective valve
3. Pilot burning,
A. Defective switch, wall switch,
valve knob
turned to
"ON", switch
is turned to
"ON" or "RS",
but burner will
not ignite.
B. Pilot flame too small
C. Defective or malfunctioning ther-
D. Defective valve
4. Frequent pilot
A. Pilot flame may be too high or too
outage prob-
lem.
5. The pilot and
A. Inner vent pipe leaking exhaust
main burner
extinguish
B. Horizontal vent improperly pitched
while in oper-
ation
C. Improper vent cap installation
54
remote control or wire
mopile
low, causing pilot safety to drop
out
gases back into system
ACTION
A. Open door and check to make sure wire is connected to ignitor.
B. Check for spark at electrode and pilot. If no spark and electrode
wire is properly connected, replace pilot assembly.
C. Check remote/manual shut off valve from fireplace. Low pressure
can be caused by bent lines, restricted lines, low pressure line
pressure. Consult with plumber or gas supplier.
D. Check Propane/LPG tank. Refill tank.
A. Check that thermocouple flame impinges on thermocouple. Clean
and/or adjust pilot for maximum flame impingement. Ensure that
the thermocouple connection at the gas valve is fully inserted and
tight.
Disconnect the thermocouple from the valve, place one millivolt
lead wire on the tip of the thermocouple and the other meter lead
wire on the thermocouple copper lead. Start the pilot and hold the
valve knob in. If the millivolt reading is less than 15 mV, replace
pilot assembly.
B. If thermocouple is producing more than 15 mV, replace faulty
valve.
A. Check switch and wire for proper connection. Place jumper wires
across terminals of switch. If burner comes on, replace defective
switch.If the switch is OK, repeat the same procedure on remote
control If burner comes on, replace remote control.
Place jumper wire across wire at gas valves (terminals marked TH
and TP/TH). If burner comes on, wires are faulty or connections
are bad. Replace wire.
B. If pilot flame is not close enough to the thermopile, adjust pilot
flame.
C. Check thermopile wire connections to make sure all are tight and
that the thermopile is fully inserted into pilot assembly. Check
thermopile with a millivolt meter. Connect leads to TP and TP/TH
terminals on the control valve. If meter reading is below 325 mV,
replace pilot assembly.
D. Turn valve knob to "On" and switch to "ON." Take a reading at
the thermopile leads (TP & TP/TH) on the valve. If the meter
reads greater than 175 mV and the burner does not light, replace
defective valve.
A. Clean and adjust the pilot flame for maximum flame impingement
on thermocouple.
A. Check for flue product leak. Replace defective pipe section.
B. Check horizontal-venting piping is running upward 1/4" per foot.
Do not run the pipe level or downward.
C. Check for proper installation and freedom from debris or blockage
56D0106

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sdv600

Table of Contents