Technical Safety Equipment; Gas Control Block; Combustion Products Discharge Safety Device - Lochinvar Knight LG30GCE Installation, Commissioning, User & Maintenance Instructions

Traditionally gas fired single flue water heater with pilot ignition
Table of Contents

Advertisement

1.2
Technical safety
equipment
1.2.1
Gas control valve
The water heater has been fitted with
a gas control block consisting of a
thermo-electrical pilot flame safeguard,
pilot flame pressure regulator, burner
pressure regulator, a control thermostat
(adjustable between 30°C and 71°C)
and a safety thermostat (82°C). This gas
control block with its simple and secure
control respectively switches the gas
supply to the main burner on or off.
This gas control block is suitable for
gasses from the first, second and third
gas family. The maximum inlet pressure
is 50 mbar.
1.2.2
Combustion products
discharge safety device
The water heater has been fitted with a
combustion products discharge safety
device. It is the function of the safety
device to prevent flue gasses from the
water heater entering the room where
the water heater has been placed,
instead of passing through the flue to
outside atmosphere. The gas supply is
disconnected as soon as the device is
activated by hot gasses flowing over
the sensor.
After the cause of the re-entry of flue
gasses has been traced the device can
be put back into operation by pressing its
reset button.
If this faillure occurs frequently, this
indicates that the flue suffers from down
draught conditions. It is recommended
that a competent person carry out the
necessary remendial action.
important
The combustion products discharge
safety device should never be put out
of operation. Re-entry of flue gasses
to the building could be harmful and
cause poisoning or death.
6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents