Top Exit Vertical Termination - Napoleon GDS28P Installation And Operating Instructions Manual

Natural and propane vented gas fireplace heaters
Table of Contents

Advertisement

3.9

TOP EXIT VERTICAL TERMINATION

Simple venting configurations.
For vent configurations requiring one or more 90° elbows the following formulas apply:
Formula 1: H
< V
T
Formula 2: H
+ V
T
Example 6:
V
= 5 FT
1
V
= 6 FT
2
V
= 10 FT
3
V
= V
+ V
+ V
= 5 + 6 + 10 = 21 FT
T
1
2
3
H
= 8 FT
1
H
= 2.5 FT
2
H
= H
+ H
= 8 + 2.5 = 10.5 FT
R
1
2
H
= .03 (four 90° elbows - 90°)
O
= .03 (360° - 90°) = 8.1 FT
H
= H
+ H
= 10.5 + 8.1 = 18.6 FT
T
R
O
H
+ V
= 18.6 + 21 = 39.6 FT
T
T
Formula 1:
Formula 2:
Since both formulas are met, this vent configuration is acceptable.
T
< 40 feet
T
H
< V
T
T
18.6 < 21
H
+ V
< 40 FT
T
T
39.6 < 40
(H
) < (V
)
T
T
See graph to determine the required vertical rise V
required horizontal run H
40
30
REQUIRED
VERTICAL
20
RISE IN
FEET V
T
10
3
0
HORIZONTAL VENT RUN PLUS OFFSET IN FEET H
The shaded area within the lines represents acceptable
90°
V
1
.
T
5
10
15
and V
values for H
T
T
90°
H
2
V
H
2
1
90°
18.1
W415-0153 / B / 06.10.10
17
for the
T
20
T
V
3
90°