DESCRIPTION
DESCRIPTION
The capacity of the MA3000, GEM-Series and Signature
5500 and SS-P Series control panels may be expanded
through the use of GEM-EZM zone expansion modules.
GEM-EZM4 modules provide up to four additional zones;
GEM-EZM8 modules, up to 8 additional zones. Four-zone
and 8-zone modules may be combined as necessary to
supply the required number of zones. Refer to the installa-
tion instructions for the control panel in use for wiring
requirements for UL-listed applications.
WIRING
WIRING
Wire the expansion zones to the module and the module
to the control panel in accordance with the wiring diagrams
using wire no thinner than #22AWG. Install end-of-line
resistors on all zones even if one or more zones are not
used.
Note: The addition of Zone Expansion Modules will re-
Note:
duce the amount of current available at the control panel's
Auxiliary Power Output terminals.
MODULE ASSIGNMENT
MODULE ASSIGNMENT
Regardless of how the modules are arranged, the expan-
sion zones are divided into consecutively-numbered
groups of four. Each 4-zone module comprises one group
of zones; each 8-zone module comprises two groups.
Every module must be assigned a unique ''base address''.
In the case of a 4-zone module, the base address number
is the same as its group number. For the 8-zone module,
the base address number will be the lower of its two group
numbers. Note that (a) groups must be numbered con-
secutively (that is, missing numbers are not permitted); and
(b) no two modules may be numbered alike.
Example. Two GEM-EZM8s and one GEM-EZM4 are used
to provide 20 expansion zones:
Groups 1 & 2
Group 3
GEM-EZM8
GEM-EZM8
GEM-EZM4
GEM-EZM4
Base Addr ''1''
Base Addr ''3''
The base address is assigned to the module by proper
selection of Address Jumpers JP1-JP5 (to the right of the
LED) in accordance with Table 1. Also refer to the Zone
Wiring Diagram.
© Napco 1997
Groups 4 & 5
GEM-EZM8
GEM-EZM8
Base Addr ''4''
INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
GEM-EZM4, GEM-EZM8
GEM-EZM4, GEM-EZM8
ZONE EXPANSION MODULES
ZONE EXPANSION MODULES
for MA3000, GEM-Series,
for MA3000, GEM-Series,
Signature S5500 & SS-P Series
Signature S5500 & SS-P Series
Control Panels
Control Panels
Base
Base
Address
Address
JP5
JP5
1
ON
2
ON
3
ON
4
ON
5
ON
6
ON
7
ON
8
ON
9
ON
10
ON
11
ON
12
ON
13
ON
14
ON
15
ON
16
OFF
17
OFF
18
OFF
19
OFF
20
OFF
21
OFF
22
OFF
Table 1. Jumper emplacement as a function of Base Address.
Table 1. Jumper emplacement as a function of Base Address.
Shaded area is not applicable to GEM-P3200 or SS-P3200.
Shaded area is not applicable to GEM-P3200 or SS-P3200.
PROGRAMMING
PROGRAMMING
The control panel must be programmed with regard to
the modules (4-zone or 8-zone) in use. Referring to the
respective Programming Workbook, program EZM TYPE to
enable the module. Starting in the first location and pro-
ceeding in succession, program a ''1'' for each 4-zone
group of expansion zones in the system. For example, if
one GEM-EZM8 is used for Zones 9 through 16 (two groups
of 4), program a ''1'' in the first and second locations (right
''nibble''). Similarly, if an GEM-EZM4 is used for Zones 17
through 20 (1 group), program a ''1'' in the third location
(right ''nibble''). Thus, each GEM-EZM4 will require a ''1'' in
only one location whereas each GEM-EZM8 will require a
WI583C 2/97
Address Jumpers
Address Jumpers
JP4
JP4
JP3
JP3
JP2
JP2
ON
ON
ON
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
JP1
JP1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON

Advertisement

loading

Summary of Contents for NAPCO GEM-Series

  • Page 1 TOLL FREE: (800) 645-9440 © Napco 1997 DESCRIPTION DESCRIPTION The capacity of the MA3000, GEM-Series and Signature 5500 and SS-P Series control panels may be expanded through the use of GEM-EZM zone expansion modules. GEM-EZM4 modules provide up to four additional zones;...
  • Page 2 ‘‘1’’ in two consecutive locations. TAMPER TAMPER If the cover is removed, the keypad sounder will pulse and the display will indicate a zone-module tamper condition along with the module number. Press [ sounder. LOOP RESPONSE LOOP RESPONSE Loop response times for Zones 1 through 8 are pro- grammed in the control panel.
  • Page 3 System Wiring Diagram. System Wiring Diagram. NOTES NOTES...
  • Page 4 NAPCO SECURITY SYSTEMS, INC. (NAPCO) warrants its prod- ucts to be free from manufacturing defects in materials and workmanship for thirty-six months following the date of manufac- ture. NAPCO will, within said period, at its option, repair or replace any product failing to operate correctly without charge to the original purchaser or user.