13.3. Protection Control For Heating Operation

13.3.1. Intake Air Temperature Control
Compressor will operate at Max frequency if below condition occur:
1. When the indoor intake air temperature is 30°C or above.
13.3.2. Outdoor Air Temperature Control
• The maximum current value is regulated when the outdoor air temperature rises above 14°C in order to avoid compressor over-
loading.
13.3.3. Overload Protection Control
• The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown in below.
• If the heat exchanger temperature exceeds 60°C, compressor will stopped.