Measuring The Ionization Current; Installing The Casing - Rinnai E75CN Installation & Servicing Instructions Manual

High efficiency condensing gas boiler
Table of Contents

Advertisement

12.4 Measuring the ionization current

12.5 Installing the casing

Installing casing
fi gure 30
Ending the O
measuring procedure:
2
-
Press the - button until
With this the procedure has ended..
-
Replace the black cover on the gas valve and secure it with the screw.
-
Switch off the system using the Central Heating button and the DHW button
-
Disconnect
the
connection
on
the
measuring
device
Select the μA direct current range on the measuring
device. The measuring device must have a resolution
of at least 1 μA.
-
Switch on the sytem using the Central Heating button
and the DHW button.
-
Press the MODE-button for 5 seconds.
-
The display will show COdE followed by an arbitrary
number;
-
Select by means of the
-
Press the Store-button to confi rm the code (code blinks 1 x);
-
Press the MODE-button until SERV is shown;
-
Press the STEP-button once until 1 is shown;
alternately 1 and OFF will be shown.
-
Press the
button until the maximum value (in kW) is achieved;
The boiler will burn on full load (value on display in kW)
-
Measure the ionization. When the boiler is in full load the ionization current must
be > 4 μA and write down this value in the log book.
-
Press the
button until OFF is shown (keep button pressed).
-
Switch off the system using the Central Heating button and the DHW button
-
Disconnect the measuring device and restore the plug and the socket connection
on the probe.
-
Switch on the sytem using the Central Heating button and the DHW button.
-
Install the cover on the boiler and close all 4 quick releases of the casing
-
Tighten the 4 screws A,B,C and D in the quick releases (fi gure 30);
-
Tighten the screw E behind the door on the front of the casing (fi gure 30);
is shown (keep button pressed).
plug
and
the
probe
and
connect
in
series.
See
fi gure
or the
button the code C123;
socket
the
29.
Ionization test
value in BTU/hr = x3415
fi gure 29
63