Electrical data

RZQ(S)71-100C
Unit combination
Indoor uni t
Outdoor uni t
SYMBOLS
MCA
: Min. Circuit Amps (A)
TOCA
: Total Over Current Amps (A)
MFA
: Max. Fuse Amps (A) (See note 7)
MSC
: MSC means the max. current during the
starting of compressor. (A)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor (A)
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
kW
: Fan Motor Rated Output (kW)
• Outdoor Units • R-410A • RZQ71-140C7V1B
Power supply
Hz-volts
Vol t age range
Max. 50Hz 264V
Min. 50Hz 198V
Max. 50Hz 264V
Min. 50Hz 198V
Max. 50Hz 264V
Min. 50Hz 198V
NOTES
1
RLA is based on the following conditions:
Power supply: 50Hz - 230V
Cooling
Indoor temperature 27°CDB/19°CWB
Outdoor temperature 35°CDB
Heating
Indoor temperature 20.0°CDB
Outdoor temperature 7.0°CDB/6.0°CWB
2
TOCA means the total value of each OC set
3
Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or
above listed operation range limits
4
Maximum allowable voltage unbalance between phases is 2%
5
MCA represents maximum input current., MFA represents capacity which may accept MCA
(next lower standard fuse rating, min.15A)
6
Select wire size based on the larger value of MCA or TOCA
7
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker)
• Split Sky Air • Outdoor Units
Comp.
MCA
TOCA
MFA
MSC
RLA
OFM
IFM
kW
FLA
kW
FLA
3D059191A
3
1
3
6