Hazardous Locations; Air For Combustion And Ventilation; Unconfined Space; Confined Space - Carrier 58UXT Installation, Start-Up, And Operating Instructions Manual

100 series
Table of Contents

Advertisement

HAZARDOUS LOCATIONS

When the furnace is installed in a residential garage, it must be
installed so that the burners and ignition source are located at least
18 in. above the floor. The furnace should be protected from
physical damage by vehicles. When a furnace is installed in public
garages, airplane hangars, or other buildings having hazardous
atmospheres, the unit must be installed in accordance with the
recommended good practice requirements of the National Fire
Protection Association, Inc.
Step 2—Air for Combustion and Ventilation
Provisions for adequate combustion and ventilation air must be
provided in accordance with Section 5.3, Air for Combustion and
Ventilation, of the NFGC or applicable provisions of the local
building codes.
Canadian installations must be in accordance with Section 7 of the
NSCNGPIC and all authorities having jurisdiction.
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and
iodide. These elements are found in aerosol sprays, deter-
gents, bleaches, cleaning solvents, salts, air fresheners, and
other household products.
All fuel-burning equipment must be supplied with air for combus-
tion of the fuel. Sufficient air MUST be provided to ensure there
will not be a negative pressure in the equipment room or space. In
addition, a positive seal MUST be made between the furnace
cabinet and the return-air duct to prevent pulling air from the
burner area and draft safeguard opening into the circulating air.
The operation of exhaust fans, kitchen ventilation fans,
clothes dryers, or fireplaces could create a negative air
pressure condition at the furnace. Make-up air must be
provided for these devices, in addition to that required by the
furnace.
The requirements for combustion and ventilation air depend upon
whether the furnace is located in a CONFINED or UNCONFINED
space.

UNCONFINED SPACE

An unconfined space must have at least 50 cu ft for each 1000
Btuh of total input for all the appliances (such as furnaces, clothes
dryers, water heaters, etc.) in the space.
For Example:
58UXT FURNACE HIGH-STAGE
INPUT BTUH
60,000
80,000
100,000
117,000
If the unconfined space is of unusually tight construction, air for
combustion and ventilation MUST come from either the outdoors
or spaces freely communicating with the outdoors. Combustion
and ventilation openings must be sized the same as for a confined
space as defined below. Return air must not be taken from the
room unless an equal or greater amount of air is supplied to the
room.

CONFINED SPACE

A confined space has volume less than 50 cu ft per 1000 Btuh of
the total input rating for all appliances installed in that space. A
MINIMUM SQ FT WITH 7-1/2 FT
CEILING
400
534
667
780
confined space MUST have 2 permanent openings, 1 within 12 in.
of the ceiling, and the other within 12 in. of the floor which freely
communicate with an unconfined space or the outdoors. (See Fig.
2.)
NOTE: In determining the free area of an opening, the blocking
effect of the louvers, grilles, and screens must be considered. If the
free area of a louver or grille design is unknown, it may be
assumed that wood louvers have a 20 percent free area, and metal
louvers or grilles have a 60 percent free area. Screens, when used,
must not be smaller than 1/4-in. mesh. Louvers and grilles must be
constructed so they cannot be closed.
The size of the openings depends upon whether the air comes from
outside of the structure or an unconfined space inside the structure.
1. All air from inside the structure:
a. Each opening MUST have at least 1 sq in. of free area per
1000 Btuh of the total input for all equipment within the
confined space, but not less than 100 sq in. per opening.
(See Fig. 2.) The minimum dimension of air openings shall
be not less than 3 in.
For Example:
COMBUSTION AIR FROM UNCONFINED SPACE
58UXT Furnace
High-Stage
Input Btuh
60,000
80,000
100,000
117,000
b. If the building is constructed unusually tight, a permanent
opening directly communicating with the outdoors should
be provided. This opening shall have a minimum free area
of 1 sq in. per 4000 Btuh of total input rating for all
equipment in the enclosure. (See Fig. 3.)
c. If the furnace is installed on a raised platform to provide a
return-air plenum, and return air is taken directly from the
hallway or space adjacent to the furnace, all air for
combustion must come from outdoors. (See Fig. 3.)
2. All air from outside the structure:
a. If combustion air is taken from outdoors through vertical
ducts, the openings and ducts MUST have at least 1 sq in.
of free area per 4000 Btuh of the total input for all
equipment within the confined space. (See Fig. 3.)
For Example:
COMBUSTION AIR FROM OUTDOORS THROUGH
VERTICAL DUCTS
58UXT Furnace
High-Stage
Input Btuh
60,000
80,000
100,000
117,000
b. If combustion air is taken from the outdoors through
horizontal ducts, the openings and ducts MUST have at
least 1 sq in. of free area per 2000 Btuh of the total input
for all equipment within the confined space. (See Fig. 3.)
4
Free Area per Opening
(Sq In.)
100
100
100
117
Free Area per Opening
Round Pipe
(Sq In.)
15.0
20.0
25.0
29.3
(In. Dia)
5
6
6
7

Advertisement

Table of Contents
loading

Table of Contents