Mitsubishi Electric PUHY-P200 Service Handbook page 92

City multi
Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

Items
Indoor
Ambient temp.
Outdoor
Quantity
Indoor unit
Quantity in operation
Model
Condition
Main pipe
Piping
Branch pipe
Total piping length
Indoor unit fan notch
Refrigerant volume
Total current
Outdoor
Volts
unit
Compressor frequency (No.1/No.2)
Indoor unit
LEV
opening
SC (LEV1)
High pressure(after O/S)
Pressure
/Low pressure(before accumulator)
Discharge (TH11/TH12)
Heat exchanger outlet (TH5)
Accumulator
Outdoor
unit
Suction (Compressor)
Sectional
temp .
Shell bottom (Compressor)
SCC outlet (TH7)
Bypass outlet (TH8)
LEV inlet
Indoor
unit
Heat exchanger outlet
Outdoor unit
DB/WB
Set
200
m
kg
A
V
Hz
324
Pulse
MPa
Inlet
Outlet
˚C
- 90 -
PUHY-P600
27.0/19.0
35.0/24.0
5
5
200
125
50
25
250
5
10
55
Hi
28.3
29.6/27.1
380/415
50Hz : 104/50
60Hz : 98/60
324
387
362
222
388
246
2.93/0.84
84/86
41
15
15
19/17
47/43
24
8
24
12
PUHY-P650
27.0/19.0
35.0/24.0
5
5
200
125
50
25
5
10
55
Hi
29.3
33.1/30.3
380/415
50Hz : 112/50
60Hz : 107/60
324
387
362
222
266
3.03/0.83
86/86
43
14
14
18/15
53/49
26
7
24
12

Hide quick links: