(4) Outdoor LEV coil removal procedure (configuration)
As shown in the figure, the outdoor LEV is made in such a way that the coils and the body can be separated.
Coils
Body
Stopper
Lead wire
Removing the coils:
Fasten the body tightly at the bottom (Part A in the figure) so that
the body will not move, then pull out the coils toward the top. If
they catch on the stopper and are difficult to take out, turn the
coils left and right until the stoppers are free from the stopper in-
dentations, then pull the coils out.
If you take out the coils without gripping the body, undue force
may be applied to the piping and the pipe may be bent, be sure to
fasten the body in such a way that it will not move.
Part A
Installing the coils :
Fasten the body tightly at the bottom (Part A in the figure) so that
the body will not move, then insert the coils from the top, inserting
the coils' stopper securely in one of the indentations on the body.
(There are four indentations for the stopper on the body around its
circumference, and it doesn't matter which indentation is used.
However, be careful not to apply undue force to the lead wires or
twist them around inside the body.) If the coils are inserted with-
out gripping the body, it may exert undue force on the piping, caus-
ing it to become bent, so be sure to hold the body firmly so that it
won't move when installing the coils.
Part A