3. Amount of additional refrigerant to be charged
At the time of shipping from the factory, the outdoor unit is charged with the amount of refrigerant shown in the
following table, but since no extension piping is included, please carry out additional charging on-site.
Outdoor unit model name
Refrigerant charge volume
Calculation formula:
Calculate the additional refrigerant volume by calculating the size of the extension liquid piping and its length (unit : m)
Additional refrigerant volume (kg) = (0.2 x L
: Length of φ 15.88 liquid pipe (m)
L
1
: Length of φ 12.7 liquid pipe (m)
L
2
: Length of φ 9.52 liquid pipe (m)
L
3
: Length of φ 6.35 liquid pipe (m)
L
4
α : Refer to the right table.
❉ In the calculation results, round up fractions smaller than 0.01kg. (Example: 14.04kg → 14.1kg)
Example:
PUHY-P650YGM-A
φ 15.88 (30m)
Each pipe is of liquid piping.
φ 15.88 : 30m
φ 12.7
: 10m
φ 9.52
: 10m + 10m + 20m + 10m + 10m = 60m
φ 6.35
: 10m
From the above calculation formula,
Additional charge volume
14.04kg obtained is converted in a unit of 0.1kg.
Therefore,
Additional charge volume
P200
P250
P300
7.0kg
9.5kg
9.5kg
) + (0.12 x L
1
Total capacity of connected indoor unit
φ 9.52 (10m)
φ 12.7 (10m)
φ 9.52
(10m)
250
= (0.2 x 30) + (0.12 x 10)+ (0.06 x 60) + (0.024 x 10) + 3 = 14.04kg
= 14.1kg
P350
P400
P450
9.5kg
13.0kg
22.0kg
) + (0.06 x L
) + (0.024 x L
2
3
~ 80
81 ~ 160
161 ~ 330
331 ~ 480
481 ~ 630
631 ~ 710
711 ~ 890
891 ~ 1070
φ 9.52
φ 9.52
(20m)
(10m)
125
80
- 83 -
P500
P550
P600
P650
22.0kg
22.0kg
22.0kg
22.0kg
) + α
4
α
1.0kg
1.5kg
2.0kg
2.5kg
3.0kg
4.0kg
5.0kg
6.0kg
φ 9.52
φ 6.35
(10m)
(10m)
63
20