[6-9 Evaluating and Adjusting Refrigerant Charge ]
(2) Example: PUHY-P350YKB-A1
Indoor 1: P125
The total length of liquid pipe of each size is as follows:
ø12.7: A + e = 40 + 10 = 50 m
ø9.52: B + C + D + a + b + d = 10 + 15 + 10 + 10 + 5 + 10 = 60 m
ø6.35: c = 10 = 10 m
A
(3) Sample calculation
Total length of liquid
Additional
refrigerant charge
=
x 0.26 (kg/m)
(kg)
0 (m) x 0.26 (kg/m)
=
= 12.5 (12.45) kg
CAUTION
Charge liquid refrigerant (as opposed to gaseous refrigerant) into the system.
If gaseous refrigerant is charged into the system, the composition of the refrigerant in the cylinder will change and may
result in performance loss.
HWE14040
a: ø9.52
A: ø12.7
40 m
2: P100
B: ø9.52
10 m
b: ø9.52
3: P40
C: ø9.52
15 m
c: ø6.35
4: P32
D: ø9.52
10 m
d: ø9.52
5: P63
e: ø12.7
B
a
b
P125
P100
Total length of liquid
+
x 0.18 (kg/m)
0 (m) x 0.18 (kg/m)
0
+
0
10 m
5 m
10 m
10 m
10 m
C
D
c
P40
Total length of liquid
Total length of liquid
+
+
x 0.11 (kg/m)
x 0.054 (kg/m)
50 (m) x 0.11 (kg/m)
60 (m) x 0.054 (kg/m)
+
50 x 0.11
+
- 134 -
e
d
P32
P63
Total length of liquid
+
x 0.021 (kg/m)
10 (m) x 0.021 (kg/m)
60 x 0.054
+
10 x 0.021
+ 0
+ 3.5
+ 0
+ 3.5
GB