Mitsubishi Electric PUHY-P200 Service Handbook page 113

Hide thumbs Also See for PUHY-P200:
Table of Contents

Advertisement

[5-2 Outdoor Unit Control ]
(2) Starting the emergency operation (When the OS is in trouble)
1) A communication error occurs. → An emergency operation starts in approximately six minutes.
Error codes that permit an emergency operation (Applicable to both OC and OS)
Trouble source
Circuit board failure or the power
to the outdoor units is off
Emergency operation pattern (2 outdoor units)
Emergency operation pattern (3 outdoor units)
OC
OS1
OS2
Cooling
Emergency
operation
Heating
Maximum total capacity
of indoor units (Note 1)
(Note 1) If an attempt is made to put into operation a group of indoor units whose total capacity exceeds the maximum allowable capacity,
some of the indoor units will go into the same condition as Thermo-OFF.
(3) Ending the emergency operation
When communication is restored, the emergency mode is cancelled, and the units go into the normal operation mode.
HWE14040
Error codes that permit an
emergency operation
6607
6608
OC
OS
Cooling
Emergency
operation
Heating
Maximum total capacity
of indoor units (Note 1)
OC failure
OS1 failure
OS2 failure
pattern
pattern
pattern
Trouble
Normal
Normal
Trouble
Normal
Normal
Permitted
Permitted
Permitted
Permitted
Permitted
Permitted
Capacity that matches the total capacity of the operable outdoor units
- 104 -
Error code description
No acknowledgement error
No response error
OC failure
OS failure
pattern
pattern
Trouble
Normal
Normal
Trouble
Permitted Permitted
Permitted Permitted
Capacity that matches
the total capacity of the
operable outdoor units
OC, OS1 failure
OC, OS2 failure
pattern
pattern
Normal
Trouble
Normal
Trouble
Trouble
Normal
Permitted
Permitted
OS1, OS2 failure
pattern
Trouble
Normal
Normal
Trouble
Trouble
Trouble
Permitted
Permitted
Permitted
Permitted
GB

Advertisement

Table of Contents
loading

Table of Contents