Commercial Air Conditioner
Model: AU55NFIAIA
5.3 Piping length and drop between units
Haier
MP2
1) When connected with 8 units,indoor units refer to <admissible combination examples>
2) Total length=l1+l2*2+l3*4+l4*4+l5*4<=100m
3) Max. piping length =(l1+l2+l3+l5)<=70m
4) Max. piping length between the indoor unit and the first branch pipe<=30m
5) Max. drop between outdoor unit and indoor unit: H<=30m(indoor above
outdoor);H<=20m(indoor below outdoor)
6) Max. drop between the two indoor units : h<=10m
7) Expansion valve is less than 15m to its corresponding indoor unit
8) Only wall mounted types are connected with expansion valves.
9) The expansion valves of different indoor models are different.
10)The first branch pipe must use FQG-180,the others use less than it.
- 27 -