Viessmann VITODENS 100-W Installation And Service Instructions Manual page 44

Wall mounted gas condensing boiler
Hide thumbs Also See for VITODENS 100-W:
Table of Contents

Advertisement

Troubleshooting
Repairs
(cont.)
20
10
8
6
4
2
1
0.8
0.6
0.4
10 30 50 70 90 110
Temperature in °C
Checking cylinder temperature sensor (gas condensing boiler)
X21
X21
X7
X7
X20
X20
5
5
44
2. Check the sensor resistance and
compare it with the curve.
3. In the case of severe deviation, drain
the boiler on the heating water side
and replace the sensor.
Danger
The boiler water temperature
sensor is immersed in the
heating water (risk of scald-
ing).
Drain the boiler before replac-
ing the sensor.
1. Remove plugs % from the cable har-
ness and check the resistance.

Advertisement

Table of Contents
loading

Table of Contents