Troubleshooting
Repairs
(cont.)
20
10
8
6
4
2
1
0.8
0.6
0.4
10 30 50 70 90 110
Temperature in °C
Checking cylinder temperature sensor (gas condensing boiler)
X21
X21
X7
X7
X20
X20
5
5
44
2. Check the sensor resistance and
compare it with the curve.
3. In the case of severe deviation, drain
the boiler on the heating water side
and replace the sensor.
Danger
The boiler water temperature
sensor is immersed in the
heating water (risk of scald-
ing).
Drain the boiler before replac-
ing the sensor.
1. Remove plugs % from the cable har-
ness and check the resistance.