Maximum Allowable Exhaust Vent Pipe Length (in ft.) Without Insulation In Unconditioned Space For
Winter Design Temperatures Single - Stage High Efficiency Furnace
Winter Design
1
Temperatures
°F (°C)
32 to 21
(0 to -6)
20 to 1
(-7 to -17)
0 to -20
(-18 to -29)
1
Refer to 99% Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook.
2
Poly-Propylene vent pipe (PP)
NOTE - Maximum uninsulated vent lengths listed may include the termination(vent pipe exterior to the structure) and cannot exceed 5 linear feet or the
maximum allowable intake or exhaust vent length listed in table 5 or 6 which ever is less.
NOTE - If insulation is required in an unconditioned space, it must be located on the pipe closest to the furnace. See figure30.
Vent Pipe
Diameter
045
2
PVC
PP
2 in.
26
24
2-1/2 in.
18
N/A
3 in.
14
12
2 in
16
15
2-1/2 in.
12
N/A
3 in.
9
8
2 in.
10
9
2-1/2 in.
8
N/A
3 in.
4
3
Conditioned
Conditioned
Space
TABLE 7
Unit Input Size
070
090
2
PVC
PP
PVC
44
41
44
32
N/A
50
26
23
38
28
26
40
20
N/A
30
16
14
26
20
18
30
14
N/A
20
10
8
16
Space
Pipe Insulation
Unconditioned
Space
FIGURE 30
Page 25
110
2
2
PP
PVC
PP
PVC
44
24
24
N/A
N/A
58
N/A
N/A
33
55
49
60
37
24
24
N/A
N/A
44
N/A
N/A
23
32
28
40
28
24
24
N/A
N/A
32
N/A
N/A
14
26
23
30
Exhaust
Pipe
Intake
Pipe
135
2
PP
N/A
N/A
53
N/A
N/A
35
N/A
N/A
26