1-17. COMPRESSOR PREHEATING

When the outdoor heat exchanger temperature is lower than 0°C and after 30 minutes has passed
after power-on or operation stop, power is applied to the compressor and the compressor is heated.
(By heating the compressor, warm air is quickly discharged when operation is started.)
When operation was started, and when the outdoor temperature rises to 2°C or greater, preheating is ended.

1-18. DEFROST OPERATION CONTROL

1. CONDITION OF STARTING THE DEFROST OPERATION
The defrost operation starts when the outdoor heat exchanger temperature sensor detects
the temperature lower than the values shown in Table 10.
(Table 10 : Condition of starting Defrost Operation)
1st time defrosting after starting operation
Compressor contiguous
operation time
Compressor integrating
operation time
Operation
temperature
Defrosting after 2nd time upon starting operation
Compressor contiguous
operation time
Compressor integrating
operation time
Operation
temperature
Integrating defrost for intermittent operation
Compressor integrating
operation time
Operating condition

2. CONDITION OF THE DEFROST OPERATION COMPLETION

Defrost operation is released when the conditions become as shown in Table 11.
(Table 11 : Defrost Release Condition)
Outdoor heat exchanger temperature sensor value is higher than +10°C or
Compressor operation time has passed 15 minutes.
Below 10 min.
Less than 17 min.
17 to 62 min.
Does not operate
Below 10 min.
Less than 35 min. 35 min. to 215min 215 min. to 4 hours
Does not operate
Less than 10 min.
OFF count of the compressor
40 times
If the compressor continuous operation time is less than 10 minutes,
the OFF number of the compressor is counted.
If any defrost operated, the compressor OFF count is cleared.
Release Condition
01-25
Above 10 min.
62 min. to 4 hours More than 4 hours
- 9°C
- 5°C
Above 10 min.
- 6°C
- 5°C
More than 210 min.
Compressor OFF
(at outside air temp.< 2°C)
- 3°C
More than 4 hours
- 3°C
=