General Information; Unit Nameplate; Compressor Nameplate; Unit Description - Trane WSC120E Installation Operation & Maintenance

Packaged heat pump 3 through 10 ton
Table of Contents

Advertisement

General Information

Unit Nameplate

A Mylar unit nameplate is located on the unit's corner support next to the filter access panel. It
includes the unit model number, serial number, electrical characteristics, refrigerant charge, as well
as other pertinent unit data.

Compressor Nameplate

The nameplate for the compressors are located on the side of the compressor.

Unit Description

Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and compressor oil,
and run tested for proper control operation.
The condenser coils are aluminum fin, mechanically bonded to copper tubing.
Direct-drive, vertical discharge condenser fans are provided with built-in thermal overload
protection.
The ReliaTel™ Control Module is a microelectronic control system that is referred to as
"Refrigeration Module" (RTRM). The acronym RTRM is used extensively throughout this
document when referring to the control system network.
These modules through Proportional/Integral control algorithms perform specific unit functions
that governs unit operation in response to; zone temperature, supply air temperature, and/or
humidity conditions depending on the application. The stages of capacity control for these units
is achieved by starting and stopping the compressors.
The RTRM is mounted in the control panel and is factory wired to the respective internal
components. The RTRM receives and interpret information from other unit modules, sensors,
remote panels, and customer binary contacts to satisfy the applicable request for cooling.
Economizer Control Actuator (Optional) ReliaTel™ Control
The ECA monitors the mixed air temperature, return air temperature, minimum position setpoint
(local or remote), power exhaust setpoint, CO2 setpoint, CO2, and ambient dry bulb/enthalpy
sensor or comparative humidity (return air humidity against ambient humidity) sensors, if
selected, to control dampers to an accuracy of +/- 5% of stroke. The actuator is spring returned to
the closed position any time that power is lost to the unit. It is capable of delivering up to 25 inch
pounds of torque and is powered by 24 VAC.
RTCI -- ReliaTel™ Trane Communication Interface (Optional)
This module is used when the application calls for an ICSTM building management type control
system. It allows the control and monitoring of the system through an ICS panel. The module can
be ordered from the factory or ordered as a kit to be field installed. Follow the installation
instruction that ships with each kit when field installation is necessary.
RLCI - ReliaTel™ LonTalk Communication Interface (Optional)
This module is used when the application calls for an ICSTM building management type control
system that is LonTalk. It allows the control and monitoring of the system through an ICS panel.
The module can be ordered from the factory or ordered as a kit to be field installed. Follow the
installation instruction that ships with each kit when field installation is necessary.
8
RT-SVX23E-EN