Table Of Clearance Reduction Percentages - Drolet DB03081 Installation And Operation Manual

Classic with blower
Table of Contents

Advertisement

Classic With Blower Installation and Operation Manual

6.4.2 Table of Clearance Reduction Percentages

Type of shield
Sheet metal, a minimum of 24
gauge (0.61 mm) in thickness ,
spaced out at least 25 mm (1 in)*
by non-combustible spacers
Ceramic tiles, or equivalent non-
combustible
material,
combustible board spaced out at
least
25 mm
(1 in)*
combustible spacers
Ceramic tiles, or equivalent non-
combustible
material,
combustible
board,
minimum of 24 gauge (0.61 mm)
sheet metal backing spaced out at
least
25 mm
(1 in)*
combustible spacers
Brick, spaced out at least 25 mm
(1 in)* by non-combustible spacers
Brick, with a minimum of 24 gauge
(0.61 mm) sheet metal backing,
spaced out at least 25 mm (1 in)*
by non-combustible spacers
* In Canada this space can be 21 mm (7/8 in)
32
Clearances may be reduced by these
Sides
and rear %
Can/US
A
(%)
67
on
non-
50
by
non-
on
non-
with
a
67
by
non-
50
67
percentages
Top %
(ceiling)
USA
Can/US
min.
A
(%)
12 in
50
18 in
33
12 in
50
18 in
N/A
12 in
N/A
USA
min.
18 in
24 in
24 in
N/A
N/A