Daikin FTXL20G2V1B Technical Data Manual page 22

Hide thumbs Also See for FTXL20G2V1B:
Table of Contents

Advertisement

3
Electrical data
RXL35G
Representative unit combination
Indoor unit
Outdoor unit
FTXL35G2V1B
RXL35G2V1B
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency (Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps (A)
W
: Fan Motor Rated Output
• Outdoor Units • R-410A • RXL-G2V1B
Power supply
Hz-volts
Voltage range
50 - 220
Max. 50Hz 264V
50 - 230
Min. 50Hz 198V
50 - 240
1. RLA is based on the following conditions:
2. Maximum allowable voltage variation between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use Circuit Breaker.
• Split Sky Air • Outdoor Units
Comp.
MCA
MFA
RHz
19.75
20
44
NOTES
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
OFM
IFM
RLA
W
FLA
W
4.0
3.8
53
0.27
23
3.6
3D059718A
FLA
2
0.15
3
23