START: Measure outdoor ambient temperature
USE WEIGH‐IN METHOD
DO NOT CHARGE UNIT
Weigh‐in or remove refrigerant
(Results of charging at low
based upon line length
temperatures not reliable)
APPROACH TXV
Once refrigerant charge is
correct, disconnect gauge set
and replace service port caps.
If refrigerant is added
or
removed,
verify
charge
using
the
Subcooling Method.
If value is LESS
than shown, add
refrigerant.
START: Measure outdoor ambient temperature
USE WEIGH‐IN METHOD
DO NOT CHARGE UNIT
Weigh‐in or remove refrigerant
(Results of charging at low
based upon line length
temperatures not reliable)
SUBCOOLING TXV
C
BLOCK OUTDOOR COIL: [sometimes necessary with lower
temperatures] Use cardboard or plastic sheet to restrict the airflow
through the outdoor coil to achieve pressures from 325-375 psig
(2240-2585 kPa). Higher pressures are needed to check charge. Block
equal sections of air intake panels and move coverings sideways until
the liquid pressure is in the above noted ranges.
Once refrigerant charge is
correct, disconnect gauge set
and replace service port caps.
If refrigerant is added or
removed, verify charge
using the Approach
Method.
If value is LESS
than shown, add
refrigerant.
507163-01 05/13
ABOVE or
BELOW
64ºF
(17.7ºC) and
Below
If value is MORE
than shown, remove
refrigerant.
MORE or
LESS
Figure 22. Using HFC-410A Approach (TXV) Charge Method
ABOVE or
BELOW
64ºF
(17.7ºC) and
Below
CARDBOARD OR
PLASTIC SHEETS
If value is MORE
than shown, remove
refrigerant.
MORE or
LESS
Figure 23. Using HFC-410A Subcooling (TXV) Charge Method
65ºF
(18.3ºC) and
Above
APPº (Approach) Values(F:+/-1.0° [C: +/-0.6°])
-036
-048
TEMP*
6 (3.3)
8 (4.4)
*Temperature of air entering outdoor
coil is 65ºF (18ºC) or above.
65ºF
(18.3ºC) and
Above
SCº (Subcooling) Values (F:+/-1.0° [C: +/-0.6°])
-036
-048
TEMP*
6 (3.3)
6 (3.3)
*Temperature of air entering outdoor
coil is 65ºF (18ºC) or above.
Page 24
1. Connect gauge set as illustrated in figure 18.
2. Confirm proper airflow across coil using figure
19.
3. Compare unit pressures with table 4, Normal
Operating Pressures.
4. Set thermostat to call for heat (must have a
cooling load between 70‐80ºF (21-26ºC).
5. When heat demand is satisfied, set thermostat
to call for cooling.
6. Allow temperatures and pressures to stabilize.
7. Record outdoor ambient temperature:
AMBº =_________
8. Record liquid line temperature:
LIQº = __________
9. Subtract to determine approach (APPº):
LIQº_____ - AMBº _____ = APPº_____
10. Compare results with table below.
-060
4 (2.2)
1. Connect gauge set as illustrated in figure 18.
2. Confirm proper airflow across coil using figure 19.
3. Compare unit pressures with table 4, Normal
Operating Pressures.
4. Set thermostat to call for heat (must have a cooling
load between 70‐80ºF (21-26ºC)
5. Measure outdoor ambient temperature
6. When heat demand is satisfied, set thermostat to
call for cooling
7. Allow temperatures and pressures to stabilize.
NOTE - If necessary, block outdoor coil to maintain
325 - 375 psig.
8. Record liquid line temperature:
LIQº = ______
9. Measure liquid line pressure and use the value to
determine saturation temperature (see table 3):
SATº = ______
10. Subtract to determine subcooling (SCº):
SATº_____ - LIQº _____ = SCº _____
11. Compare results with table below.
-060