UTICA BOILERS PEG075EID Installation, Operation & Maintenance Manual page 21

Peg-e series gas-fired steam boilers
Table of Contents

Advertisement

Adjust Steam Pressure Control
• Steam pressure limit control (pressuretrol) shuts
off gas to main burners when steam pressure in
boiler reaches cut-off setpoint (i.e. sum of cut-in and
differential setpoints).
• Burners refire when steam pressure drops to cut-in
setpoint.
• System pressure requirements are based on size and
condition of pipes, and load.
• Cut-in setting of pressuretrol should never be less than
twice system pressure drop for good system operation.
A. In typical single family residence with clean one-
pipe heating system and cast iron radiation, cut-in
is usually set at minimum setting, i.e. 1/2 psi.
• Steam radiation is sized based on square feet of
equivalent direct radiation (EDR). This is based on
steam pressure in the radiator of just less than 2 psi.
• Set differential adjustment at 1 psi, i.e. steam pressure
required in radiators. Results in cut-off setpoint of 1½
psi.
• Larger systems or other types of systems such as two
pipe systems, or systems with convectors or fan coil
units, pressuretrol settings need to be determined on
system-by-system basis.
• Cut-in setpoint is determined by system pressure drop
to furthest radiator or terminal unit. Double system
pressure drop as safety factor, resulting in the rule
cut-in setting should never be less than twice system
pressure drop.
• Differential setpoint is steam pressure required at
terminal heating units.
Boiler will now operate in correct pressure range. It
maintains enough steam pressure to send steam out to
furthest radiator, and not go over optimum steam pressure
required at the radiators.
CHECKING AND ADJUSTING
Checking Controls
Low Water Cut-Off
A. Turn off power to boiler or turn thermostat down to
B. Drain water to below visible bottom of water gauge
C. Gas valve opens for approximately 15 seconds
D. When water is restored, it waits 30 seconds before
Boiler Equipped With Optional VXT-24 Water Feeder
E. Continue thermostat call for heat after low water
F. One minute time delay, water feeder starts feeding
G. Feeder feeds for one minute, and then goes into
H. Cycle of alternately waiting and feeding will repeat
• In either case, one and two inches of water should
be visible in glass gauge when both water feeder is
satisfied, and burners are allowed to ignite.
• Time delays in feed cycles are designed to prevent
boiler from flooding due to slow return lines.
• To check pressure limit, run boiler until pressure
reaches system demand. Turn pressure screw and drop
pressure setting until boiler shuts down. This shows the
pressure limit is operating properly.
• Refer to control manufacturer's instructions for more
information.
Check Thermostat Operation
Thermostat set above temperature indicated on
thermometer, boiler should ignite.
Verify thermostat turns boiler off when room temperature
reaches selected setting and starts boiler operating when
room temperature falls few degrees.
Set thermostat for desired temperature. Conditions in your
home and location of thermostat will govern this setting.
21
lowest setting.
glass. Turn power on and turn thermostat to call for
heat.
(time delay on probe type LWCO), gas valve will
close and red indicator illuminates on LWCO.
reactivating burner circuit.
cut off recognizes low water condition.
water to boiler.
another one minute waiting period.
until the water level in boiler rises and makes
contact with probe, satisfying water feeder and
igniting burners.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Peg150eidPeg187eidPeg225eidPeg112eidPeg262eidPeg299eid

Table of Contents