Boiler Ratings & Capacities - UTICA BOILERS SFH-3085 Installation, Operation & Maintenance Manual

Starfire iv series 4 water oil fired cast iron boiler
Table of Contents

Advertisement

BOILER
MODEL
NUMBER
SFH-3085W
SFH-3085WT
SFH-3100W
SFH-3100WT
SFH-4100W
SFH-4100WT
SFH-4125W
SFH-4125WT
SFH-4145W
SFH-4145WT
SFH-5160W
SFH-5160WT
SFH-5185W
SFH-5185WT
SFH-6175W
SFH-6175WT
SFH-6210W
SFH-6210WT
*
Mbh = 1,000 Btu per hour
Oil burner input based on 140,000 Btu per gallon.
1
Net AHRI water ratings shown are based on a piping and pickup allowance of 1.15. Consult manufacturer
2
before selecting a boiler for installation having unusual piping and pickup requirements, such as intermittent
system operation, extensive piping systems, etc.
Heating Capacity and AFUE based on 13.0% CO2 with -0.02" W. C. draft over fire and #1 smoke or less.
3
Tested in accordance with U.S. Department of Energy test procedures.
T= Tankless
STANDARD EQUIPMENT: Crated Boiler, Flush Jacket, Oil Burner, Target Wall/Liner, Circulator- 1¼", Safety
Relief Valve, Temperature Pressure Gauge, Drain Valve, Wiring Harness, Burner Electrical Disconnect, Plastic
Cover, Supply Tapping-2", Return Tapping-1 1/2", High Limit and Circulator Control, Primary Control. For
Tankless Heater Units add Tankless Hot Water Coil and Triple Combination High Limit/Low Limit/Circulator
Control.
BOILER
MODEL
NUMBER
SFH-3085WT
SFH-3100WT
SFH-4100WT
SFH-4125WT
SFH-4145WT
SFH-5160WT
SFH-5185WT
SFH-6175WT
SFH-6210WT
BOILER RATINGS & CAPACITIES
BOILER RATINGS
(1)
OIL BURNER
INPUT
gph
0.85
1.00
1.00
1.25
1.45
1.60
1.85
1.75
2.10
[Btu = British Thermal Unit]
TANKLESS WATER HEATER CAPACITIES
INPUT
TANKLESS
RATE
HEATER
G.P.H.
NUMBER
0.85
T3
1.00
T3
1.00
T4
1.25
T4
1.45
T4
1.60
T4
1.85
T4
1.75
T4
2.10
T4
(3)
HEATING
CAPACITY
*Mbh
*Mbh
119
103
140
119
140
122
175
151
203
173
224
193
259
221
245
212
294
252
TANKLESS
HEATER CAPACITY
INTERMITTENT DRAW
G.P.M.
4
(2)
NET
(3)
RATINGS
A.F.U.E.
WATER
*Mbh
90
85.0%
103
84.0%
106
86.0%
131
85.0%
150
84.0%
168
85.0%
192
84.0%
184
85.0%
219
84.0%
WATER CONTENT
3
4
4
CHIMNEY
8X8X15
8X8X15
8X8X15
8X8X15
8X8X15
8X8X15
8X8X15
8X8X15
8X8X15
BOILER
GALS.
10.5
10.5
13.5
13.5
13.5
16.5
16.5
19.5
19.5

Advertisement

Table of Contents
loading

Table of Contents