5-3. RAS-13UKP-ES3 / RAS-13UA-ES3

RAS-13UKP-AS3 / RAS-13UA-AS3

Cooling
0.39m
(Connecting pipe)
∅12.7
O.D.:12.7mm
Packed valve
Cooling
Cooling Compressor
Cooling
50Hz
Standard
Cooling
Overload
Low temperature
Note :
•ı Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
P
(∅12.7)
PA150X2T-4FM1
Condenser
Propeller fan
Outdoor unit
Standar d
pressure P
(MPaG)
0.90
1.03
0.70
T1
Indoor unit
Heat exchanger
Cross flow fan
Mark(
Surface temp. of heat
exchang er inter changing
pipe T1 (°C)
9.0
13.0
2.0
− 19 −
FILE NO. SVM-04001
Packed valve
(∅6.35)
Capillary tube
∅1.5x500
l
Refrigerant
R410A : 0.95 kg.
)means check points of Gas Leak.
Ambient temp.
conditions DB/WB
Fan speed
(indoor)
Indoor
High
27/19
High
32/23
Low
21/15
0.49m
(Connecting pipe)
∅6.35
O.D.:6.35mm
(°C)
Outdoor
35/24
43/26
21/15