Centralized Group No. Setting - Daikin Sky Air B-Series R-410A Service Manual

Split system air conditioners
Table of Contents

Advertisement

Method of Field Set (Reset after Maintenance Inspection/Repair)
1.6

Centralized Group No. Setting

Centralized
1. If the inspection/test button is pushed for 4 seconds or more when in the normal mode,
Group No. Setting
2. Using the temperature control buttons, set the mode No. to "00."
by Remote
3. Push the inspection/test button to inspect the group No. display.
Controller
4. Using the programming time button, set the group No. for each group. (Group No. rises in
5. Push the timer ON/OFF button and enter the selected group No.
6. Push the inspection/test button and return to the normal mode.
∗ If the address has to be set individually for each unit for power consumption counting, etc., set
the mode No. to "30."
Group No. Setting
Example
Note:
1. "F1,F2" indicates interface adaptor for SkyAir series.
2. If not using remote controllers, temporarily connect a remote controller to set the group No.,
64
If carrying out centralized control with a central remote controller and unified ON/OFF
controller, you have to set the group No. for each group by remote controller.
To set the group No., first turn on the power supply of the central remote controller, unified
ON/OFF controller and indoor unit.
operation enters the "field set mode."
the order of 1-00, 1-01, ...1-15, 2-00 ...4-15, etc. The unified ON/OFF controller however
displays only the range of group numbers selected by the switch for setting each address.)
Group No.
Central remote controller
Unified ON/OFF controller
set the group No. for centralized control, and then disconnect the controller.
Indoor unit
Group No. for
centralized
control
No remote controller
Remote controller centralized control
(automatic address)
Si21-205
MODE NO.
FIELD
SET
MODE
Field Setting