SUBcOOLinG chARGinG in cOOLinG ABOVE 55°F Od AMBiEnt
The Trane company has always recommended installing
Trane approved matched indoor and outdoor systems.
All Trane split systems are ARI rated with only TXV indoor
systems.
The benefits of installing approved indoor and outdoor split
systems are maximum efficiency, optimum performance and
the best overall system reliability.
The following charging methods are therefore
prescribed for systems with indoor TXVs.
1. Subcooling (in the cooling mode) is the
only recommended method of charging
above 55°F ambient temperatures.
2. For best results - the indoor temperature
should be kept between 70°F to 80°F. Add
system heat if needed.
3. At start-up, or whenever charge is
removed or added, the system must be
operated for a minimum twenty (20)
minutes to stabilize before accurate
measurements can be made.
4. Measure Liquid Line Temperature and
Refrigerant Pressure at service valves.
5. Determine total refrigerant line length,
and height (lift) if indoor section is above
the condenser.
6. Determine the Design Subcool Charging
Temperature from the unit nameplate.
7. Locate this value in the appropriate
column of the Subcooling Charging Table.
Locate your liquid line temperature
in the left column of the table, and the
intersecting liquid line pressure under
your nameplate subcool value column.
Add refrigerant to raise the pressure to
SUBCOOL CHARGING TABLE CORRECTIONS FOR LINE LENGTH AND RISE
60
50
40
30
25
20
15
10
0
Subtract 10 psig from S.C. Table Pressure
10
6
LIQUID
TEMP
˚
(
F)
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
Installer's Guide for charging method.
Use Design Subcool Value from Table
20
25
TOTAL REFRIGERANT LINE LENGTH (FEET)
match the table, or remove refrigerant to lower the
pressure. Again, wait twenty (20) minutes for the
system conditions to stabilize before adjusting charge
again.
8. When system is correctly charged, you can refer to
System Pressure Curves (in Service Facts) to verify
typical performance.
R-410A REFRIGERANT CHARGING CHART
DESIGN SUBCOOLING (
8
9
10
LIQUID GAGE PRESSURE (PSI)
179
182
185
195
198
201
211
215
218
229
232
236
247
251
255
267
271
275
287
291
296
309
313
318
331
336
341
355
360
365
381
386
391
407
413
418
435
441
446
464
470
476
495
501
507
Refer to Service Facts or
Add 10 psig to Subcool Charging Table Pressure
30
40
˚
F)
11
12
13
188
191
195
204
208
211
222
225
229
240
243
247
259
263
267
279
283
287
300
304
309
322
327
331
346
351
355
370
376
381
396
402
407
424
429
435
452
458
464
482
488
495
514
520
527
From Dwg. D154557P01 Rev. 2
60
80
18-AC71D1-5
14
198
215
232
251
271
291
313
336
360
386
413
441
470
501
533