Table 16 — Fan Performance 50HJQ006 — Vertical Discharge Units; High-Static Motor (Belt Drive)
AIRFLOW
0.2
(Cfm)
Rpm
Bhp
1500
789
0.40
1600
826
0.46
1700
865
0.54
1800
905
0.62
1900
946
0.72
2000
984
0.82
2100
1024
0.93
2200
1064
1.05
2300
1104
1.18
2400
1145
1.32
2500
1186
1.48
AIRFLOW
1.2
(Cfm)
Rpm
Bhp
1500
1221
1.17
1600
1252
1.27
1700
1278
1.37
1800
1303
1.48
1900
1330
1.59
2000
1362
1.73
2100
1393
1.80
2200
1423
2.02
2300
1454
2.18
2400
1485
2.36
2500
1518
2.55
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-
supplied drive.
NOTES:
1. Boldface indicates field-supplied drive is required.
2.
indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casings, and wet coils.
See Table 8 for accessory/FIOP static pressure information.
EXTERNAL STATIC PRESSURE (in. wg)
0.4
Watts
Rpm
Bhp
Watts
429
896
0.53
572
501
931
0.61
645
582
966
0.69
736
674
1002
0.78
838
777
1037
0.88
940
889
1072
0.98
1063
1012
1108
1.10
1196
1145
1145
1.22
1328
1288
1183
1.36
1502
1441
1222
1.45
1645
1604
1262
1.68
1819
EXTERNAL STATIC PRESSURE (in. wg)
1.4
Watts
Rpm
Bhp
Watts
1216
1256
1.30
1492
1308
1311
1.45
1523
1420
1345
1.57
1615
1553
1371
1.69
1747
1676
1396
1.80
1891
1809
1422
1.94
2034
1952
1452
2.08
2167
2126
1483
2.24
2350
2310
1515
2.41
2698
2524
1544
2.59
2948
3010
1575
2.78
3522
0.6
Rpm
Bhp
Watts
Rpm
990
0.67
705
1072
1020
0.75
797
1101
1051
0.84
899
1133
1084
0.93
1001
1163
1119
1.04
1124
1194
1154
1.16
1247
1226
1192
1.29
1380
1259
1225
1.43
1523
1294
1260
1.57
1686
1330
1296
1.73
1860
1365
1331
1.80
2044
1400
1.6
Rpm
Bhp
Watts
Rpm
1280
1.32
1757
1320
1340
1.58
1800
1380
1397
1.76
1850
1424
1433
1.90
1952
1480
1460
2.03
2095
1517
1485
2.16
2258
1544
1510
2.31
2501
1569
1538
2.46
2688
1595
1569
2.64
3091
1622
1601
2.84
3379
1652
1631
3.03
4036
1684
4. Maximum continuous bhp is 2.9 and the maximum continuous
watts are 2615. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized
with confidence. Using your fan motors up to the wattage rat-
ings shown will not result in nuisance tripping or premature
motor failure. Unit warranty will not be affected. See Tables 6
and 7 for additional information.
5. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative for details.
6. Interpolation is permissible. Do not extrapolate.
24
0.8
1.0
Bhp
Watts
Rpm
Bhp
0.83
869
1153
1.00
0.91
961
1178
1.09
1.01
1053
1206
1.18
1.10
1155
1235
1.29
1.21
1288
1266
1.40
1.33
1431
1297
1.53
1.47
1574
1327
1.66
1.62
1737
1359
1.80
1.78
1901
1392
1.97
1.94
2074
1426
2.15
2.12
2269
1461
2.34
2.0
1.8
Bhp
Watts
Rpm
Bhp
1.22
1944
1360
1.33
1.61
2047
1421
1.76
1.89
2070
1467
2.06
2.09
2197
1524
2.28
2.25
2358
1562
2.46
2.40
2542
1590
2.62
2.55
2821
1616
2.79
2.71
3031
1643
2.96
2.88
3486
1671
3.15
3.07
3715
3.28
3970
Watts
1032
1134
1237
1349
1461
1604
1758
1931
2115
2310
2504
Watts
2164
2280
2305
2446
2625
2830
3141
3375
3881

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents