Daikin FTX25JVEA9 Service Manual page 227

Super multi plus j series
Hide thumbs Also See for FTX25JVEA9:
Table of Contents

Advertisement

Method of Field Set
2.1.2 Local Setting Mode No.
Example
To set the filter sign time to "filter contamination - heavy" for all units in a group:
Set mode No. to "10," setting switch No. to "0," and setting position No. to "02."
Table
Mode
Setting
No.
Switch
Note 1
No.
10(20)
0
Filter contamination - heavy /
light (Setting of operating hours
for filter sign indication)
(Change setting when reducing
filter sign indication time to half
due to quick soiling of filter)
1
Long-life filter type (Setting of filter sign
indication time)
(Change setting when Ultra-long-life filter is
installed)
3
Estimation of filter operating hour
(Change setting when filter sign indication is
not used)
11(21)
0
No. of Sky Air indoor units connected for
simultaneous ON-OFF multi system
(Change setting when simultaneous
operation multi system is used) *Note 3
1
Simultaneous operation multi-unit individual
setting
2
Indoor unit fan OFF when cooling/heating is
OFF
12(22)
3
Change to set fan speed when heater
thermostat is OFF *Note 5
5
Automatic restart after power outage reset
*Note 6
13(23)
0
High
Ceiling
Fan speed increase (wall-mounted type)
1
Air flow direction selection (Change setting
when blocking kit is installed) *Note 4
3
Air flow direction adjustment (Change setting
when decorative air outlet panel is installed)
4
Setting of air flow direction adjustment range
5
On-site fan speed change by air outlet
(When using phase control)
6
External static pressure setting (To be set
according to connected duct resistance)
(High ceiling setting in the case of FHYK)
Notes:
1. Setting is made in all units in a group. To set for individual indoor units or to check the
2. The setting position No. is set to "01" at the factory, except for the following cases in which
"
"
"
"
214
Setting Description
Ultra-Long-
Life Type
Long-Life
Type
Standard
Type
Ceiling-mounted built-in multi-flow
cassette type, Ceiling suspended
cassette type
Ceiling-suspended type, wall-
mounted type
setting, use the mode Nos. (with "2" in upper digit) in parentheses ( ).
"02" is set.
Setting of air flow direction adjustment range
Automatic restart after power outage.
Remote control thermostat
Filter sign indication (only for ceiling-mounted duct type)
Setting Position No. *Note 2
01
Light
Approx.
Heavy
10,000
hours
Approx.
2,500
hours
Approx.
200
hours
Long-Life Filter
Ultra-Long-Life
Filter (1)
ON
Pair
Unified
Individual
Fan OFF
Fan Speed LL
Set Fan Speed
OFF
N
2.7 m or Lower
2.7~3.5 m
Standard
Slight Increase
F
Installed
Not Installed
Upward
Standard
Standard
Option 1
Standard
High Static
(Standard)
Pressure (High
Ceiling Setting)
Si18-201
02
03
Approx.
5,000
hours
Approx.
1,250
hours
Approx.
100
hours
Setting Description
Ultra-Long-Life
Filter (2)
OFF
Twin
Triple
ON
H
S
Normal Increase
T
W
Downward
Option 2
Low Static Pressure
Operating Test