Maintenance - Carrier OBL098 Installation Instructions Manual

Low boy oil furnace
Hide thumbs Also See for OBL098:
Table of Contents

Advertisement

3.3.5
OVERFIRE
PRESSURE TEST
The overfire draft that is taken through the observation
port,
located above the burner, is a measurement
necessary
to
determine
if there is a blockage in the heat exchanger or the
flue pipe. Refer to the Technical Specifications
in this manual
for overfire pressure values. A high pressure condition may be
caused by excessive combustion air, due to the air band being
too wide open, or a lack of flue draft (chimney effect) or some
other blockage, such as soot in the secondary section of the
heat exchanger
or the use of an oversize nozzle input or high
pressure pump.
3.3.6
VENT TEMPERATURE
TEST
1.
2.
After having
adjusted
the burner
combustion,
insert
a
thermometer
into the test hole in the breech pipe;
The total vent temperature
should be between 204 and
302°C (400 and 575°F).
If not, check for improper
air
temperature
rise, pump pressure, nozzle size or a badly
sooted heat exchanger.
Also
refer to section
2.5 for
proper flue pipe sizing.
CAUTION
Low flue gas temperature
increases
the risk of
condensation.
Adjust the total flue gas temperature
at or higher then 204°C (400°F) in order for the heat
exchanger warranty to remain in force.
3.3.7
1.
2.
3.
4.
5.
SUPPLY
AIR TEMPERATURE
RISE TEST
Operate the burner for at least 10 minutes;
Measure the air temperature in the return air plenum;
Measuring the air temperature
in the largest trunk coming
off the supply air plenum, just outside the range of radiant
heat from the heat exchanger.
0.3 m (12") from the
plenum of the main take-off is usually sufficient;
The temperature
rise is calculated
by subtracting
the
return air temperature from the supply air temperature;
If
the
temperature
rise
is
lower
or
exceeds
the
temperature specified in Table 1, p. 13, change to the next
lower or higher blower speed tap, until the temperature
rise falls to the target. If the excessive temperature
rise
cannot be increased or reduced by changing fan speed,
investigate for ductwork obstructions,
dirty or improper air
filter, improper firing caused by improper pump pressure
or nozzle sizing.
3.3.8
LIMIT CONTROL
CHECK
After operating the furnace for at least 15 minutes, restrict the
return air supply by blocking the filters or the return air register
and allow the furnace to shut off on High Limit. The burner will
shut off but the blower wilt continue to run.
Remove the obstruction
and the burner should restart after a
few minutes. The time required for the restart also depends on
the adjustment of the blower "OFF" delay.
3.3.9
RESTART AFTER BURNER FAILURE
1.
Set the thermostat lower than room temperature;
2.
Press the reset button on the burner primary control
(relay)
3.
Set the thermostat higher than room temperature;
4.
If the burner motor does not start or ignition fails, turn
off the disconnect switch and CALL A QUALIFIED
SERVICE TECHNICIAN.
CAUTION
Do not attempt to start the burner when excess oil has
accumulated,
when the furnace is full of vapour or when
the combustion chamber is hot.
4
MAINTENANCE
I Electrical shock hazard.
I
Turn OFF power and fuel to the furnace
before any
disassembly
or servicing.
Failure to do so can result in death,
bodily
injury I
and/or property damage.
I
Preventive
maintenance
is the
best
way
to
avoid
unnecessary
expense
and
inconvenience.
Have your
heating
system
and
burner
inspected
by a qualified
service technician at regular intervals.
To maintain the reliability and optimal performance of the
furnace, have a complete
combustion
check done after
the annual maintenance call. Do not attempt to repair the
furnace or its controls. Call a qualified service technician.
Before calling for repair service check the following points:
1.
Check the oil tank gauge and make sure that the
valve is open;
2.
Check fuses and the circuit breaker;
3.
Check if the main disconnect switch is ON ;
4.
Set the thermostat above room temperature;
5.
If ignition
does not occur, turn off the disconnect
switch and call a qualified service technician.
When ordering replacement
parts, please specify the
complete furnace model number and serial number.