Clearances - Monessen Hearth WDV500 Installation And Operating Instructions Manual

Wdv wideview direct vent gas fireplace
Table of Contents

Advertisement

WDV Series Gas Fireplace
clearances tO cOMBustIBles
Follow these instructions carefully to ensure safe installation. Failure to
follow instructions exactly can create a fire hazard.
the appliance cannot be installed on a carpet, tile or other combustible
material other than wood flooring. If installed on carpet or vinyl flooring,
the appliance shall be installed on a metal, wood or noncombustible
material panel extending full width and depth of the appliance.
54" Minimum 
Ceiling
12" Max.
Depth
6" Min.
FP41
Figure 4 -
Ceiling and Sidewall Clearances
FP2421
mantel clearances
Mantel clearances
nOte: the combustible area above the facing must not protrude more than 3/4" from the
facing. If it does, it is considered a mantel and must meet the mantel requirements listed in
this manual.
8
2
/
" Max Depth
1
2
12" Min.
From Opening
6" Min.
From Opening
5 "
Min. to Combustibles
Wall
12"
6"
12"
9"
6"
Top of Fireplace
Opening
side View
FP43
1"
2 "
Side of Fire-
place Opening
top View
Figure 5 -
Mantel clearances
FP2423
mantel leg

clearances

Stud
Insulation
Board
Standoff
2
1
/
"
2
FP4
FP2422
mantel clearances
1 "
3
"
4
"
45°
3"
5"
6"
78D0011