SMMS 2-way Air Discharge Cassette Type
With a remote controller-less system (group control)
Besides the switching method using the wired remote controller as a way to establish the high-ceiling and filter
settings, switching is also possible by changing over the short plug settings on the indoor printed circuit board as
shown in the following table.
* However, once these settings are changed, 0001 can be set easily, but bear in mind that to return to the 0000 data,
it will be necessary to change the short plugs over to the standard (factory setting) positions and rewrite the data
back to SET DATA 0000 from the wired remote controller.
• Change over the short plugs on the indoor printed circuit board, and select the desired setting.
Short plug positions (CN112, CN111 and CN110 from the left)
Short plug
position
Short Open
SET DATA
Ceiling height
Standard filter
Filter
(Factory setting)
EN-45
0000
0001
3.2 m
(AP007 to AP030)
2.7 m
3.0 m
(AP036 to AP056)
Super long life filter
23
Change of lighting time of filter
sign
According to the installation condition, the lighting time of
the filter sign (Notification of filter cleaning) can be
changed.
Follow the basic operation procedure
(1 → 2 → 3 → 4 → 5 → 6).
• For the CODE No. in Procedure 3, specify [01].
• For the SET DATA in Procedure 4, select the SET
DATA of Filter sign lighting time from the following
table.
SET DATA
0000
0001
0002
0003
0004
To secure better effect of heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator, etc. to circulate heat air
near the ceiling.
0003
Follow the basic operation procedure
3.8 m
(1 → 2 → 3 → 4 → 5 → 6).
(AP007 to AP030)
• For the CODE No. in Procedure 3, specify [06].
• For the SET DATA in Procedure 4, select the SET
3.5 m
DATA of Detection temp shift value to be set up from
(AP036 to AP056)
the following table.
SET DATA
0000
0001
0002
0003
0004
0005
0006

Group control

In a group control, a remote controller can control up to
maximum 8 units.
• For wiring procedure and wiring method of the
individual line (Identical refrigerant line) system, refer
to "ELECTRICAL WORK" in this Manual.
• Wiring between indoor units in a group is performed in
the following procedure.
Connect the indoor units by connecting the remote
controller inter-unit wires from the remote controller
terminal blocks (A/B) of the indoor unit connected with
a remote controller to the remote controller terminal
blocks (A/B) of the other indoor unit. (Non-polarity)
Filter sign lighting time
• For address setup, refer to the Installation Manual
None
attached to the outdoor unit.
150 hours
2500 hours (Factory setting)
Ventilator (procured locally)
5000 hours
Select this setting when a locally procured ventilator has
10000 hours
been connected.
Follow the basic operation procedure
(1 → 2 → 3 → 4 → 5 → 6).
• For the CODE No. in Procedure 3, specify [31].
• Select "0001" as the SET DATA in procedure 4.
SET DATA
0000
0001
Detection temp shift value
No shift
+1°C
+2°C (Factory setting)
+3°C
+4°C
+5°C
+6°C
Installation Manual
Ventilator
Not provided (Factory setting)
Provided
EN-46