SMMS 2-way Air Discharge Cassette Type
CAUTION
When pouring the water, pour it slowly. If it is poured with too much force, it will spread around the inside of the indoor
unit, possibly causing the unit to malfunction.
Drain pan
Tool for pouring water
Bottle
Water (1500 cc to 2000 cc)
EN-31
Insert the hose end between the heat
exchanger and the drain pan, and
then bend the hose downward.
Power supply wiring
Float switch connector
(3P) (CN34: red)
Perform heat insulating
• As shown in the figure, cover the flexible hose and hose band with the attached heat insulator up to the bottom of
the indoor unit tightly.
• Cover the drain pipe tightly with a heat insulator procured locally so that it overlaps with the attached heat insulator
of the drain connecting section.
Wrap the attached heat insulator tightly from the
surface of the indoor unit.
16
Heat insulator of the
Heat insulator
drain connecting section
(Procured locally)
(Accessory)