Connect The Cable To The Outdoor Unit - Panasonic CS-E7NKR Service Manual

Hide thumbs Also See for CS-E7NKR:
Table of Contents

Advertisement

4
Close the Low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the
gauge does not move after approximately five minutes.
Note: BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERENT GAS LEAKAGE.
5
Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve.
6
Tighten the service port caps of the 3-way valve at a torque of 18 N•m with a torque wrench.
7
Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to "OPEN"
using a hexagonal wrench (4 mm).
8
Mount valve caps onto the 2-way valve and the 3-way valve.
Be sure to check for gas leakage.
o
If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in the step
-
If the leak stops when the piping connections are tightened further, continue working from step
-
If the leak does not stop when the connections are retightened, repair location of leak.
-
Do not release refrigerant during piping work for installation and reinstallation.
-
Take care of the liquid refrigerant, it may cause frostbite.
11.3.4

Connect the cable to the Outdoor Unit

1
Remove the control board cover from the unit by loosening the screw.
2
Cable connection to the power supply through Isolating Devices (Disconnecting means).
Connect approved type polychloroprene sheathed power supply cord 3 x 1.5 mm
o
3 x 2.5 mm
connect the others end of the cord to Isolating Devices (Disconnecting means).
3
Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed
2
4 x 1.5 mm
flexible cord, type designation 245 IEC 57 or heavier cord.
4
Connecting cable between outdoor unit and DRED (Demand response enabling devices) shall be double
insulation layer, polychloroprene sheathed (>50V) with size 4 x (0.5 mm
where the maximum allowable length is 30m.
5
Connect the power supply cord and connecting cable between indoor unit and outdoor unit according to the
diagram below.
2
(2.0 ~ 2.5HP) type designation 245 IEC 57 or heavier cord to the terminal board, and
2
70
above take the following measure:
.
2
(3/4 ~ 1.75HP) or
2
to 2.0 mm
) cable or flexible cord,