Operation; General Description; Figure 51 Single Module Block Diagram (Dual Input Configuration) - Liebert NX User Manual

40-200kva, 480v, 60hz
Hide thumbs Also See for NX:
Table of Contents

Advertisement

9.0
O
PERATION
9.1

General Description

Liebert's NX provides continuous, high-quality AC power to your business-critical equipment, such as
telecommunications and data processing equipment. The Liebert NX UPS supplies power that is free
of the disturbances and variations in voltage and frequency common to utility power, which is subject
to brownouts, blackouts, surges and sags.
The Liebert NX utilizes the latest in high-frequency, double-conversion pulse width modulation
technology and fully digital controls to enhance its reliability and increase the ease of use.
Specifically, the Liebert NX 480V utilizes soft-switching technology to greatly enhance efficiency.
As shown in Figure 51, the AC utility source is input at CB1 and the rectifier converts the AC utility
into DC power. The inverter converts that DC power from the utility—or DC power from the
batteries—into AC power for the load. The batteries power the load through the inverter in the event
of a power failure. The utility source can also power the load through the static bypass.
If maintenance or repair of the UPS is necessary, the load can be switched without interruption in
service to the maintenance bypass.

Figure 51 Single module block diagram (dual input configuration)

3-Phase
3W + Gnd
3-Phase
3W + Gnd
AC Input
UPS Cabinet
Battery Cabinet
®
Liebert
NX
Internal Maintenance Bypass
Static Bypass
Rectifier
2W + Gnd
Inverter
Converter
77

Operation

3-Phase
3W + Gnd
AC Output