Filter Performance - York PS8 Technical Manual

Gas-fired high efficiency single stage downflow furnaces
Table of Contents

Advertisement

036-21610-001 Rev. A (0804)
BLOWER PERFORMANCE CFM - (WITHOUT FILTER)
MODELS
Speed
Input/Output/
Tap
Airflow/cabinet
HIGH
40/32/1200/"A" †
MED-HIGH
60/48/1200/"A" †
MED-LOW
80/64/1200/"A" †
LOW
HIGH
80/64/1600/"B" †
MED
LOW
HIGH
100/80/1200/"B" †
MED
LOW
HIGH
115/92/1600/"C"
MED
LOW
HIGH
100/80/2000/"C" †
MED
115/92/2000/"C" †
LOW
HIGH
130/104/2000/"D" †
MED
LOW
NOTE: Data below reflects airflows with two return openings - two sides or one side and bottom
HIGH
80/64/2000/"C"
100/80/2000/"C" †
MED
115/92/2000/"C" †
LOW
HIGH
130/104/2000/"D" †
MED
LOW
Indicates models available in LoNOx.
NOTES:
1. Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m
2. Return air is through side opposite motor (left side).
3. Airflows above 1800 CFM (50.97 m
4. Motor voltage at 115 V.
5. NR = Operation at this static pressure is not recommended.
BLK
BLK (HOT)
WHT
WHT (NEUTRAL)
GRN
GRN
4
EXTERNAL STATIC PRESSURE, INCHES WC
0.1
0.2
0.3
cfm
cfm
cfm
1580
1530
1470
1110
1100
1075
845
840
830
675
665
660
1970
1935
1900
1445
1435
1425
1245
1235
1225
1675
1645
1595
1270
1260
1250
955
950
945
2040
1975
1925
1725
1685
1650
1365
1355
1325
2400
2320
2275
2050
2025
1980
1690
1675
1660
2380
2330
2270
2040
2010
1980
1690
1680
1655
2405
2340
2275
2005
1990
1965
1655
1640
1625
2385
2335
2275
2005
1980
1955
1640
1635
1620
3
/min) require either return from two sides or one side plus bottom.
NOMINAL
120 VOLT
0.4
0.5
0.6
cfm
cfm
cfm
1405
1330
1245
1060
1030
980
815
790
750
645
620
585
1850
1795
1735
1415
1405
1375
1215
1205
1190
1530
1465
1385
1240
1215
1185
935
920
905
1855
1780
1695
1610
1555
1500
1290
1265
1250
2200
2115
2025
1930
1855
1805
1630
1610
1560
2205
2120
2025
1920
1875
1790
1630
1590
1530
2210
2130
2050
1935
1880
1815
1610
1585
1540
2195
2120
2040
1905
1845
1775
1605
1575
1540
3
/min).

FILTER PERFORMANCE

The airflow capacity data published in the "Blower Perfor-
mance" table listed above represents blower performance
WITHOUT filters. To determine the approximate blower per-
formance of the system, apply the filter drop value for the fil-
ter being used or select an appropriate value from the "Filter
Performance" table shown below.
NOTE: The filter pressure drop values in the "Filter Perfor-
mance" table shown below are typical values for the type of
filter listed and should only be used as a guideline. Actual
pressure drop ratings for each filter type vary between filter
manufacturer.
0.7
0.8
0.9
cfm
cfm
cfm
1150
1045
890
920
835
680
670
595
480
530
455
360
1660
1590
1495
1350
1300
1240
1170
1135
1090
1280
1155
1025
1125
1035
910
865
810
685
1610
1505
1380
1425
1340
1220
1210
1140
1045
1930
1825
1700
1720
1635
1530
1500
1430
1330
1920
1815
1705
1705
1610
1515
1490
1425
1350
1955
1840
1725
1725
1635
1535
1485
1420
1340
1935
1820
1700
1700
1610
1500
1480
1400
1330
Unitary Products Group
1.0
cfm
650
520
320
255
1395
1160
995
810
695
510
1225
1075
940
1570
1400
1225
1565
1385
1235
1600
1410
1235