FLOOR PROTECTOR

Your wood stove should be placed on a 1 inch, non-combustible surface with a k factor of 0.84.
For multiple layers, add R-values of each layer to determine the overall R-value. The R value for
the required board is 1.2. The floor protector should be under the stove, 18 inches beyond the front
and 8 inches beyond each side of the fuel loading and ash removal opening. If there is a horizontal
section of chimney connector, the floor protector should go under it and two inches beyond each side
Convert specification to R-value:
k-factor is given with a required thickness (T) in inches: R=1/k x T
C-factor is given: R=1/C
Example:
If the floor protector is 4" brick with a C-factor of 1.25 over 1/8" mineral board with a "k"
factor
of 0.29 the total R-value of the system is:
4" brick C=1.25, R=1/1.25=0.8
1/8" mineral board K=0.29, R=1/0.29 x 0.125=0.431
Total R = Rbrick + Rmineral = 0.8 + 0.431 = 1.231
Total R is greater than 1.2, the system is acceptable.
The floor protector should exceed the stove as follows:
8
FRONT
18"
(457mm)
SIDES
8"
(203mm)
(203mm)
REAR
8"
Ussc