Reduced Clearances (Canada Only) - USSC Magnolia 2015 Owner's Operation And Instruction Manual

Hide thumbs Also See for Magnolia 2015:
Table of Contents

Advertisement

REDUCED CLEARANCES (CANADA ONLY)

Check with your local regulatory authority about reducing clearances. You may decrease the
clearances by installing heat radiation shields between the walls or the ceiling and the stove. These
heat radiation shields must be installed permanently, and can include sheet metal, a rigid non-
combustible sheet or a masonry wall. Clearances of not less than 1" (25mm) and not more than 3"
(76mm) between the bottom of the shield and the floor and not less than 3" (76mm) between the top
of the shield and the ceiling must be respected to allow vertical air circulation behind the shield. The
shield must extend 20" (500mm) above the stove top and 18" (450mm) to each side of the stove.
Following the installation of such a heat radiation shield, the clearances mentioned on the stove
certification plate may be reduced as stated in the following table.
TYPE OF PROTECTION
Sheet metal, a minimum of 0.013" (0.33 mm) spaced out at
least 7/8" (21 mm) by non-combustible spacers.
Ceramic tiles, or an equivalent non-combustible material on
fire-proof supports spaced out at least 7/8" (21 mm) by non-
combustible spacers.
Ceramic tiles, or an equivalent non-combustible material
on fire-proof supports with a minimum of 0.013" (0.33 mm)
sheet metal backing spaced out at least 7/8" (21 mm) by
non-combustible spacers.
Brick spaced out at least 7/8" (21 mm) by noncombustible
spacers.
Brick with a minimum of 0,013" (0,33 mm) sheet metal backing
spaced out at least 7/8" (21 mm) by noncombustible
spacers.
10
Reducing Clearances With
Shielding
Sides and Rear/
Back
67%
50%
67%
50%
67%
Top
50%
33%
50%
N/A
N/A
Ussc

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents