SYSTEM OPERATIONAL MODES

Air conditioner systems have four modes of operation. Heat pumps have five operational modes. These modes are:
*
Auto
*
Cooling
*
Dehumidification
*
Fan
*
Heat (HP model only)
AUTO MODE
Auto Mode - Non-adjustable indoor temperature set points are 68F°and 77°F (20°C and 25°C)
NOTE — Reversing valve is de-energized in cooling mode and energized in heating mode.
Delays that normally protect the compressor are disabled during defrost cycles:
1. Minimum three (3) minute compressor time delay between operating cycles.
2. Minimum six (6) minute compressor run time between operating cycles.
If room ambient temperature is equal to or greater than 77°F (25°C), the unit cycles cooling ON. When the room ambient
temperature is equal to or less than 77°F (25°C) minus 3.6°F (2°C), the compressor will cycle OFF, the outdoor fan will cycle
OFF 60 seconds later. The indoor fan will run continuously at a preset speed until system has a heating demand or Auto Mode
is switched OFF.
If room temperature is equal to or less than 64°F (18°C) plus 3.6°F (2 C), the heating will cycle ON when room temperature is
equal to or greater than 64°F (18°C) plus 9.0°F (5°C), the compressor will cycle OFF. The outdoor fan will cycle OFF 60
seconds later. The indoor fan will cycle OFF after 60 seconds on low speed.

IV. SYSTEM OPERATION AND SERVICE

Protective Functions
Auto — Cool
Auto — Heat
AUTO MODE
FIGURE 49
Page 35
Corp. 1244-L9