Three-Way
Diverter Valve
Head
Clip
Wiring Harness
Fits Here
Wiring Harness
Fits Here
Three-Way
Diverter Valve
© Baxi Heating UK Limited 2005
Fig. 55
Spigot
Gasket
Fig. 56
13.0
Changing Components
13.10
Three-Way Diverter Valve (Head Only)
(Fig. 55)
If only the head needs replacing:
1. Unplug the wiring harness from the 3-way diverter
valve.
2.Depress the clip and revolve the head through 30°
and remove.
3. Fit replacement head and reassemble in reverse
order.
13.11
Three-Way Diverter Valve (Complete)
(Fig. 56)
1. Drain the boiler (see Section 13.1 paragraph 2 & 3).
2. Unplug the wiring harness from the 3-way diverter
valve.
3. Remove the four socket screws retaining the 3-way
valve.
4. Remove the 3-way valve.
5. Fit the new 3-way valve ensuring the gasket is in
place and that the spigots are at the top to fit into the
recesses on the manifold and reassemble in reverse
order.
41